Performed Maitenence on system. Cleaned/treated drain line and primary drain pan. Could not access the end of the drain line due to brush and plants being in the way. Cleaned condenser coils. Evaporator coils are clean but very damaged. Verified safety float switch functionality. Checked amp draw on compressor. Checked amp draw on fan motor. Checked capacitor is within factory range. Inspected Contactar. Contactar is chattering and at the end of its life span, we recommend replacing. Found low voltage wires exposed to the elements and we recommend making new connections while also sealing the wire in the condenser service panel. Made sure all connections are tight. System is cooling with an 18° temperature split at this time.

Blower wheel is very impacted with debris and growth. Recommending cleaning
Performed Maitenence on system. Cleaned/treated drain line and primary drain pan. Could not access the end of the drain line due to brush and plants being in the way. Cleaned condenser coils. Evaporator coils are clean but very damaged. Verified safety float switch functionality. Checked amp draw on compressor. Checked amp draw on fan motor. Checked capacitor is within factory range. Inspected Contactar. Contactar is chattering and at the end of its life span, we recommend replacing. Found low voltage wires exposed to the elements and we recommend making new connections while also sealing the wire in the condenser service panel. Made sure all connections are tight. System is cooling with an 18° temperature split at this time.

Blower wheel is very impacted with debris and growth. Recommending cleaning
Michael A.
Michael A. Checked in
Performed Maitenence on system. Cleaned/treated drain line and primary drain pan. Could not access the end of the drain line due to brush and plants being in the way. Cleaned condenser coils. Evaporator coils are clean but very damaged. Verified safety float switch functionality. Checked amp draw on compressor. Checked amp draw on fan motor. Checked capacitor is within factory range. Inspected Contactar. Contactar is chattering and at the end of its life span, we recommend replacing. Found low voltage wires exposed to the elements and we recommend making new connections while also sealing the wire in the condenser service panel. Made sure all connections are tight. System is cooling with an 18° temperature split at this time. Blower wheel is very impacted with debris and growth. Recommending cleaning
Clearwater, FL 33760
Upon my insection, client had another company performing is on the system for roughly 2 years. On their last visit, they recommended replacing the disconnect breaker at the unit, performing an evaporator coil cleaning, performing a blower assembly cleaning, installing a UV light, and adding refrigerant.

Upon my inspection, found disconnect not grounded properly and reconnected ground wire. Disconnect is in working condition. 
Unit has a 20° temperature split. Evaporator coils are slightly impacted with debris and the blower wheel assembly is slightly impacted with debris and bacterial growth. We recommend an evaporator coil cleaning, Blower assembly removal and cleaning, as well as a UV air Purifier inside the system to prevent the growth from returning. 

Amp draws are good, capacitor is within factory range, contactar is in good shape. 

Sending quotes for cleanings and Maitenence service agreement

Waived $95 per office request with repair
Upon my insection, client had another company performing is on the system for roughly 2 years. On their last visit, they recommended replacing the disconnect breaker at the unit, performing an evaporator coil cleaning, performing a blower assembly cleaning, installing a UV light, and adding refrigerant.

Upon my inspection, found disconnect not grounded properly and reconnected ground wire. Disconnect is in working condition. 
Unit has a 20° temperature split. Evaporator coils are slightly impacted with debris and the blower wheel assembly is slightly impacted with debris and bacterial growth. We recommend an evaporator coil cleaning, Blower assembly removal and cleaning, as well as a UV air Purifier inside the system to prevent the growth from returning. 

Amp draws are good, capacitor is within factory range, contactar is in good shape. 

Sending quotes for cleanings and Maitenence service agreement

Waived $95 per office request with repair
Michael A.
Michael A. Checked in
Upon my insection, client had another company performing is on the system for roughly 2 years. On their last visit, they recommended replacing the disconnect breaker at the unit, performing an evaporator coil cleaning, performing a blower assembly cleaning, installing a UV light, and adding refrigerant. Upon my inspection, found disconnect not grounded properly and reconnected ground wire. Disconnect is in working condition. Unit has a 20° temperature split. Evaporator coils are slightly impacted with debris and the blower wheel assembly is slightly impacted with debris and bacterial growth. We recommend an evaporator coil cleaning, Blower assembly removal and cleaning, as well as a UV air Purifier inside the system to prevent the growth from returning. Amp draws are good, capacitor is within factory range, contactar is in good shape. Sending quotes for cleanings and Maitenence service agreement Waived $95 per office request with repair
Clearwater, FL 33765
Ricky O.
Ricky O. Checked in
Found unit not cooling due to bad float switch not allowing system to come on. I replaced float switch and verified operation. Client just wants system running as they are moving tomorrow. System is cooling
Clearwater, FL 33763
Clearwater, FL - Installed uv air purification inside air handler #2.
Michael A.
Michael A. Checked in
Installed uv air purification inside air handler #2.
Clearwater, FL 33761
Ruud 3 ton heat pump
15 seer
10 year parts warranty
3 year labor warranty 
*Green cash price*
-Hurricane pad 
-Hurricane tiedowns
-UV rated armorflex
-Screw line cover back to home and silicone gaps
-New hang kit
-Drain pan
-Safeties
-Flush drain
-Keep existing filter system
-Seal to existing plenums 
-100% satisfaction guarantee
Ruud 3 ton heat pump
15 seer
10 year parts warranty
3 year labor warranty 
*Green cash price*
-Hurricane pad 
-Hurricane tiedowns
-UV rated armorflex
-Screw line cover back to home and silicone gaps
-New hang kit
-Drain pan
-Safeties
-Flush drain
-Keep existing filter system
-Seal to existing plenums 
-100% satisfaction guarantee
Martin W.
Martin W. Checked in
Ruud 3 ton heat pump 15 seer 10 year parts warranty 3 year labor warranty *Green cash price* -Hurricane pad -Hurricane tiedowns -UV rated armorflex -Screw line cover back to home and silicone gaps -New hang kit -Drain pan -Safeties -Flush drain -Keep existing filter system -Seal to existing plenums -100% satisfaction guarantee
Clearwater, FL 33755
Performed Maitenence on system. Cleaned/treated drain line and primary drain pan. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switch functionality. Checked amp draw on compressor. Checked amp draw on fan motor. Checked capacitor is within factory range. Inspected Contactar. Made sure all connections are tight. System is cooling with a 20° temperature split at this time.

Condenser coils were very impacted with debris.  Deep cleaned as part of the Maitenence for this time only. If coils get this bad next time we will have to charge extra for cleaning. 

Quote sent over for Maitenence plan.
Performed Maitenence on system. Cleaned/treated drain line and primary drain pan. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switch functionality. Checked amp draw on compressor. Checked amp draw on fan motor. Checked capacitor is within factory range. Inspected Contactar. Made sure all connections are tight. System is cooling with a 20° temperature split at this time.

Condenser coils were very impacted with debris.  Deep cleaned as part of the Maitenence for this time only. If coils get this bad next time we will have to charge extra for cleaning. 

Quote sent over for Maitenence plan.
Michael A.
Michael A. Checked in
Performed Maitenence on system. Cleaned/treated drain line and primary drain pan. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switch functionality. Checked amp draw on compressor. Checked amp draw on fan motor. Checked capacitor is within factory range. Inspected Contactar. Made sure all connections are tight. System is cooling with a 20° temperature split at this time. Condenser coils were very impacted with debris. Deep cleaned as part of the Maitenence for this time only. If coils get this bad next time we will have to charge extra for cleaning. Quote sent over for Maitenence plan.
Clearwater, FL 33760
Found system freezing up due to severely clogged and impacted evaporator coils. System may also be low on refrigerant but we cannot accurately determine without proper air flow. Found lizard burnt on contactar and capacitor near its max tolerance limit. 
System cannot cool properly at this time. Client would like a system replacement estimate. Quote has been sent over.
Found system freezing up due to severely clogged and impacted evaporator coils. System may also be low on refrigerant but we cannot accurately determine without proper air flow. Found lizard burnt on contactar and capacitor near its max tolerance limit. 
System cannot cool properly at this time. Client would like a system replacement estimate. Quote has been sent over.
Michael A.
Michael A. Checked in
Found system freezing up due to severely clogged and impacted evaporator coils. System may also be low on refrigerant but we cannot accurately determine without proper air flow. Found lizard burnt on contactar and capacitor near its max tolerance limit. System cannot cool properly at this time. Client would like a system replacement estimate. Quote has been sent over.
Clearwater, FL 33756
I checked entire system and found no issues. All previous work done looks good. Cap and wiring good. Td 19. Explained to client not to reset breakers if this happens again just call us immediately and we will come out with no service fee
I checked entire system and found no issues. All previous work done looks good. Cap and wiring good. Td 19. Explained to client not to reset breakers if this happens again just call us immediately and we will come out with no service fee
Ricky O.
Ricky O. Checked in
I checked entire system and found no issues. All previous work done looks good. Cap and wiring good. Td 19. Explained to client not to reset breakers if this happens again just call us immediately and we will come out with no service fee
Clearwater, FL 33760
Upon my inspection, found severely clogged drain that was tripping the safety float switch. Also found evaporator coils are severely clogged, condenser coils dirty, and bare wires at the condenser disconnect causing the breaker to trip. 
Performed drain cleaning, removed faulty wires from disconnect, cleaned condenser coils, and performed Maitenence on system for first membership Maitenence. 
Capacitor is within factory range. Compressor amps are good. Fan motor amps were over its max rating due to dirty condenser coils. 

Client is aware of the severity of the evaporator coils and will schedule as soon as he is ready. 
System is cooling at this time with a 19° temp split. 

When we return to clean evaporator coils, we will re route the lineset connections and pvc connection to allow for filters to be installed directly underneath the coils.
Upon my inspection, found severely clogged drain that was tripping the safety float switch. Also found evaporator coils are severely clogged, condenser coils dirty, and bare wires at the condenser disconnect causing the breaker to trip. 
Performed drain cleaning, removed faulty wires from disconnect, cleaned condenser coils, and performed Maitenence on system for first membership Maitenence. 
Capacitor is within factory range. Compressor amps are good. Fan motor amps were over its max rating due to dirty condenser coils. 

Client is aware of the severity of the evaporator coils and will schedule as soon as he is ready. 
System is cooling at this time with a 19° temp split. 

When we return to clean evaporator coils, we will re route the lineset connections and pvc connection to allow for filters to be installed directly underneath the coils.
Michael A.
Michael A. Checked in
Upon my inspection, found severely clogged drain that was tripping the safety float switch. Also found evaporator coils are severely clogged, condenser coils dirty, and bare wires at the condenser disconnect causing the breaker to trip. Performed drain cleaning, removed faulty wires from disconnect, cleaned condenser coils, and performed Maitenence on system for first membership Maitenence. Capacitor is within factory range. Compressor amps are good. Fan motor amps were over its max rating due to dirty condenser coils. Client is aware of the severity of the evaporator coils and will schedule as soon as he is ready. System is cooling at this time with a 19° temp split. When we return to clean evaporator coils, we will re route the lineset connections and pvc connection to allow for filters to be installed directly underneath the coils.
Clearwater, FL 33756
Performed Maitenence on system. System is working as best as it can given its age and condition. High compressor amps on start up. 
Client would like to invest in new system and duct work but needs to figure out finances first. 
System is cooling at this time.
Performed Maitenence on system. System is working as best as it can given its age and condition. High compressor amps on start up. 
Client would like to invest in new system and duct work but needs to figure out finances first. 
System is cooling at this time.
Michael A.
Michael A. Checked in
Performed Maitenence on system. System is working as best as it can given its age and condition. High compressor amps on start up. Client would like to invest in new system and duct work but needs to figure out finances first. System is cooling at this time.
Clearwater, FL 33764
Clearwater, FL - Install customer supplied ceiling fan and run a new line from a receptacle
Griffin K.
Griffin K. Checked in
Install customer supplied ceiling fan and run a new line from a receptacle
Clearwater, FL 33765
Upon my inspection, found indoor 3amp fuse blown. Found short at condenser contactar. Replaced contactar and fuse. Verified system is cooling at this time. System has a 16° temperature split.
Upon my inspection, found indoor 3amp fuse blown. Found short at condenser contactar. Replaced contactar and fuse. Verified system is cooling at this time. System has a 16° temperature split.
Michael A.
Michael A. Checked in
Upon my inspection, found indoor 3amp fuse blown. Found short at condenser contactar. Replaced contactar and fuse. Verified system is cooling at this time. System has a 16° temperature split.
Clearwater, FL 33763
Installed new warranty evap coil. Charged with new refrigerant. New drain connections off of unit. System is cooling with a 20° temperature split and target superheat. Found weak capacitor but client would not like to replace at this time. 
Performed full Maitenence on system. Checked amp draws, inspected wiring, checked capacitor, cleaned condenser coils, cleaned and treated drain line.
Installed new warranty evap coil. Charged with new refrigerant. New drain connections off of unit. System is cooling with a 20° temperature split and target superheat. Found weak capacitor but client would not like to replace at this time. 
Performed full Maitenence on system. Checked amp draws, inspected wiring, checked capacitor, cleaned condenser coils, cleaned and treated drain line.
Michael A.
Michael A. Checked in
Installed new warranty evap coil. Charged with new refrigerant. New drain connections off of unit. System is cooling with a 20° temperature split and target superheat. Found weak capacitor but client would not like to replace at this time. Performed full Maitenence on system. Checked amp draws, inspected wiring, checked capacitor, cleaned condenser coils, cleaned and treated drain line.
Clearwater, FL 33756
Performed leak search and found refrigerant leak in coil. Applied leak search fee to repair. 
Will return Friday to install new evaporator coil and refrigerant.
Performed leak search and found refrigerant leak in coil. Applied leak search fee to repair. 
Will return Friday to install new evaporator coil and refrigerant.
Michael A.
Michael A. Checked in
Performed leak search and found refrigerant leak in coil. Applied leak search fee to repair. Will return Friday to install new evaporator coil and refrigerant.
Clearwater, FL 33756
Scope of work:
- Remove and replace variable speed blower motor
- Remove and replace condenser start/run capacitor. 
*No guarantee on system running properly as compressor could have sustained irreversible damage during operation with a faulty blower motor and capacitor.*

System is cooling properly at this time. Good amp draws on fan motors and compressor. 

Cleaned and sanitized blower wheel complimentary
Scope of work:
- Remove and replace variable speed blower motor
- Remove and replace condenser start/run capacitor. 
*No guarantee on system running properly as compressor could have sustained irreversible damage during operation with a faulty blower motor and capacitor.*

System is cooling properly at this time. Good amp draws on fan motors and compressor. 

Cleaned and sanitized blower wheel complimentary
Michael A.
Michael A. Checked in
Scope of work: - Remove and replace variable speed blower motor - Remove and replace condenser start/run capacitor. *No guarantee on system running properly as compressor could have sustained irreversible damage during operation with a faulty blower motor and capacitor.* System is cooling properly at this time. Good amp draws on fan motors and compressor. Cleaned and sanitized blower wheel complimentary
Clearwater, FL 33761

Diagnosed bad variable speed blower motor and bad condenser capacitor. Quote sent and approved for replacement. System is 11 years old and client would like to have his own guys replace system and would like us to repair at this time. 
Waiving $95 off sold quote for repair. 

No guarantee on system running prior to repair due to system running with a faulty blower motor and bad capacitor.

Diagnosed bad variable speed blower motor and bad condenser capacitor. Quote sent and approved for replacement. System is 11 years old and client would like to have his own guys replace system and would like us to repair at this time. 
Waiving $95 off sold quote for repair. 

No guarantee on system running prior to repair due to system running with a faulty blower motor and bad capacitor.
Michael A.
Michael A. Checked in
Diagnosed bad variable speed blower motor and bad condenser capacitor. Quote sent and approved for replacement. System is 11 years old and client would like to have his own guys replace system and would like us to repair at this time. Waiving $95 off sold quote for repair. No guarantee on system running prior to repair due to system running with a faulty blower motor and bad capacitor.
Clearwater, FL 33761
Performed Maitenence on all 5 systems
Left side of building
System #1: trane
- weak blower motor capacitor 18 out of 20 6% max tolerance
- Very dirty and impacted fan blower wheel
- Very dirty and restrictive evaporator coils
Sending quote for new system replacement. 
Client has on concerns with air flow on this system and wanted to move duct work. Recommended replacing system first as the system is restricted of air flow due to impacted coils and blower wheel. 

System #2 ruud
- Very dirty and impacted fan blower wheel

Right side of building

System #1 ruud
- No issues or inefficiencies
System #2 ruud
- No issues or inefficiencies
System #3 trane
- Very dirty and impacted fan blower wheel
- Very dirty and restrictive evaporator coils
Performed Maitenence on all 5 systems
Left side of building
System #1: trane
- weak blower motor capacitor 18 out of 20 6% max tolerance
- Very dirty and impacted fan blower wheel
- Very dirty and restrictive evaporator coils
Sending quote for new system replacement. 
Client has on concerns with air flow on this system and wanted to move duct work. Recommended replacing system first as the system is restricted of air flow due to impacted coils and blower wheel. 

System #2 ruud
- Very dirty and impacted fan blower wheel

Right side of building

System #1 ruud
- No issues or inefficiencies
System #2 ruud
- No issues or inefficiencies
System #3 trane
- Very dirty and impacted fan blower wheel
- Very dirty and restrictive evaporator coils
Michael A.
Michael A. Checked in
Performed Maitenence on all 5 systems Left side of building System #1: trane - weak blower motor capacitor 18 out of 20 6% max tolerance - Very dirty and impacted fan blower wheel - Very dirty and restrictive evaporator coils Sending quote for new system replacement. Client has on concerns with air flow on this system and wanted to move duct work. Recommended replacing system first as the system is restricted of air flow due to impacted coils and blower wheel. System #2 ruud - Very dirty and impacted fan blower wheel Right side of building System #1 ruud - No issues or inefficiencies System #2 ruud - No issues or inefficiencies System #3 trane - Very dirty and impacted fan blower wheel - Very dirty and restrictive evaporator coils
Clearwater, FL 33762
Duct sealing unit#2 ductwork
Cleaning on air handler #1
UV air treatment system #1

Scope of work:
- Mastic seal all duct work on system #2 (master bedroom). 
- Clean and sanitize Air handler #1 of all growth 
- Install UV system inside Air handler #1
Duct sealing unit#2 ductwork
Cleaning on air handler #1
UV air treatment system #1

Scope of work:
- Mastic seal all duct work on system #2 (master bedroom). 
- Clean and sanitize Air handler #1 of all growth 
- Install UV system inside Air handler #1
Michael A.
Michael A. Checked in
Duct sealing unit#2 ductwork Cleaning on air handler #1 UV air treatment system #1 Scope of work: - Mastic seal all duct work on system #2 (master bedroom). - Clean and sanitize Air handler #1 of all growth - Install UV system inside Air handler #1
Clearwater, FL 33759
Outdoor unit not operating due to failed contactor. Replaced contactor and system began to run. System is currently cooling but not to full capacity. 

Unit is 11 Years Old (Out of Manufacture Warranty)

Goodman 4T (System does not look to be professionally installed)

Tested capacitor (within specifications)

Cleaned outdoor service department 

Notes 
-outdoor coils impacted with debris (affecting outdoor airflow)
-compressor internals sound like they are grinding (explained that I cannot guarantee how long it will last but can give estimate to replace compressor)
-outdoor wiring spliced and exposed 
-suction line lacking insulation 
-air handler coils impacted with debris (affecting indoor airflow)
-blower wheel and assembly impacted with bacterial growth/debris 
-secondary drain pan has no safety switch (potential water damage if primary fails)
-4” media filter needs to be replaced 
-System has no filter drier installed to capture oil back to compressor 
Ductwork 
-ducting collapse
Outdoor unit not operating due to failed contactor. Replaced contactor and system began to run. System is currently cooling but not to full capacity. 

Unit is 11 Years Old (Out of Manufacture Warranty)

Goodman 4T (System does not look to be professionally installed)

Tested capacitor (within specifications)

Cleaned outdoor service department 

Notes 
-outdoor coils impacted with debris (affecting outdoor airflow)
-compressor internals sound like they are grinding (explained that I cannot guarantee how long it will last but can give estimate to replace compressor)
-outdoor wiring spliced and exposed 
-suction line lacking insulation 
-air handler coils impacted with debris (affecting indoor airflow)
-blower wheel and assembly impacted with bacterial growth/debris 
-secondary drain pan has no safety switch (potential water damage if primary fails)
-4” media filter needs to be replaced 
-System has no filter drier installed to capture oil back to compressor 
Ductwork 
-ducting collapse
Nathan A.
Nathan A. Checked in
Outdoor unit not operating due to failed contactor. Replaced contactor and system began to run. System is currently cooling but not to full capacity. Unit is 11 Years Old (Out of Manufacture Warranty) Goodman 4T (System does not look to be professionally installed) Tested capacitor (within specifications) Cleaned outdoor service department Notes -outdoor coils impacted with debris (affecting outdoor airflow) -compressor internals sound like they are grinding (explained that I cannot guarantee how long it will last but can give estimate to replace compressor) -outdoor wiring spliced and exposed -suction line lacking insulation -air handler coils impacted with debris (affecting indoor airflow) -blower wheel and assembly impacted with bacterial growth/debris -secondary drain pan has no safety switch (potential water damage if primary fails) -4” media filter needs to be replaced -System has no filter drier installed to capture oil back to compressor Ductwork -ducting collapse
Clearwater, FL 33760
Upon my inspection, found condenser #2 breaker tripped. All wires are tight. Client said there have been many power outages in the area. Recommended replacing the breaker and installing surge protection. 

Performed Maitenences on systems. Cleaned/treated drain lines and primary drain pans. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switchs functionality. Checked amp draw on compressors. Checked amp draw on fan motors. Checked capacitors are within factory range. Made sure all connections are tight. Systems are cooling with 20° temperature splits at this time. Verified systems heat properly. 
After installing surge protectors and new breaker, system run properly. Waited 15 minutes to test breaker and breaker did not trip. 

Scope of work:
- Install two surge protectors on condenser unit disconnects
- Install new 20 amp breaker for condenser #2
Upon my inspection, found condenser #2 breaker tripped. All wires are tight. Client said there have been many power outages in the area. Recommended replacing the breaker and installing surge protection. 

Performed Maitenences on systems. Cleaned/treated drain lines and primary drain pans. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switchs functionality. Checked amp draw on compressors. Checked amp draw on fan motors. Checked capacitors are within factory range. Made sure all connections are tight. Systems are cooling with 20° temperature splits at this time. Verified systems heat properly. 
After installing surge protectors and new breaker, system run properly. Waited 15 minutes to test breaker and breaker did not trip. 

Scope of work:
- Install two surge protectors on condenser unit disconnects
- Install new 20 amp breaker for condenser #2
Michael A.
Michael A. Checked in
Upon my inspection, found condenser #2 breaker tripped. All wires are tight. Client said there have been many power outages in the area. Recommended replacing the breaker and installing surge protection. Performed Maitenences on systems. Cleaned/treated drain lines and primary drain pans. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switchs functionality. Checked amp draw on compressors. Checked amp draw on fan motors. Checked capacitors are within factory range. Made sure all connections are tight. Systems are cooling with 20° temperature splits at this time. Verified systems heat properly. After installing surge protectors and new breaker, system run properly. Waited 15 minutes to test breaker and breaker did not trip. Scope of work: - Install two surge protectors on condenser unit disconnects - Install new 20 amp breaker for condenser #2
Clearwater, FL 33759
Scope of work:
- Manually tape and mastic seal one major hole in return duct. 
- No guarantee on repair due to duct work age and condition. 
- Advised client to leave system off for two hours to allow mastic to cure
Scope of work:
- Manually tape and mastic seal one major hole in return duct. 
- No guarantee on repair due to duct work age and condition. 
- Advised client to leave system off for two hours to allow mastic to cure
Michael A.
Michael A. Checked in
Scope of work: - Manually tape and mastic seal one major hole in return duct. - No guarantee on repair due to duct work age and condition. - Advised client to leave system off for two hours to allow mastic to cure
Clearwater, FL 33764
Full system tuneup 

Wiped Down Air Handler 

Checked temperature splits 

Inspected Air Handler Coils 

Inspected Blower Wheel & Assembly 

Checked cap mfd 

Checked contactor 

Inspected wiring 

Compressor amps 

Motor amps 

Cleaned condenser coils 

Cleared drain line and pan 

Checked refrigerant pressures 

Checked blower amps 

Checked filter 

Thermostat operations 

Checked heating and cooling 

Unit is operating at this time 

*complaint about mildew smell when system runs. Home built in 2015 and new system 2022. Previous home owner had pets. Would recommend duct sanitizing and adding air scrubber to supply plenum.
Full system tuneup 

Wiped Down Air Handler 

Checked temperature splits 

Inspected Air Handler Coils 

Inspected Blower Wheel & Assembly 

Checked cap mfd 

Checked contactor 

Inspected wiring 

Compressor amps 

Motor amps 

Cleaned condenser coils 

Cleared drain line and pan 

Checked refrigerant pressures 

Checked blower amps 

Checked filter 

Thermostat operations 

Checked heating and cooling 

Unit is operating at this time 

*complaint about mildew smell when system runs. Home built in 2015 and new system 2022. Previous home owner had pets. Would recommend duct sanitizing and adding air scrubber to supply plenum.
Nathan A.
Nathan A. Checked in
Full system tuneup Wiped Down Air Handler Checked temperature splits Inspected Air Handler Coils Inspected Blower Wheel & Assembly Checked cap mfd Checked contactor Inspected wiring Compressor amps Motor amps Cleaned condenser coils Cleared drain line and pan Checked refrigerant pressures Checked blower amps Checked filter Thermostat operations Checked heating and cooling Unit is operating at this time *complaint about mildew smell when system runs. Home built in 2015 and new system 2022. Previous home owner had pets. Would recommend duct sanitizing and adding air scrubber to supply plenum.
Clearwater, FL 33760
Scope of work:
- Remove blower wheel on unit#2 and deep clean/sanitize.
- Clean/Sanitize inside both air handler units.
- Installer one UV system inside air handler #1. 
Will return to install uv system in air handler #2 after a new system is installed by the home builder.
Scope of work:
- Remove blower wheel on unit#2 and deep clean/sanitize.
- Clean/Sanitize inside both air handler units.
- Installer one UV system inside air handler #1. 
Will return to install uv system in air handler #2 after a new system is installed by the home builder.
Michael A.
Michael A. Checked in
Scope of work: - Remove blower wheel on unit#2 and deep clean/sanitize. - Clean/Sanitize inside both air handler units. - Installer one UV system inside air handler #1. Will return to install uv system in air handler #2 after a new system is installed by the home builder.
Clearwater, FL 33761
Performed Maitenences on systems. Cleaned/treated drain lines and primary drain pans. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switchs functionality. Checked amp draw on compressors. Compressors are over amping on start up exceeding the factory max LRA amp draw. Checked amp draw on fan motors. Checked capacitors are within factory range. Capacitor on Condenser #2 is out of its tolerance limit of 6% and recommending replacement. Made sure all connections are tight. Systems are cooling with 20° and 19° temperature splits at this time. Verified systems heat properly. 
Found growth inside of air handler units and growth on unit #2 blower wheel. Quote sent for cleanings and uv system installs. Client accepted quote. 

Recommending soft start kits on both condenser units to bring down the start up amp draw and prolong the life of the compressors. 
Quote sent for soft start kits. 
Quote sent for capacitor replacement. 

Inspected system #2 duct work and syste
Performed Maitenences on systems. Cleaned/treated drain lines and primary drain pans. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switchs functionality. Checked amp draw on compressors. Compressors are over amping on start up exceeding the factory max LRA amp draw. Checked amp draw on fan motors. Checked capacitors are within factory range. Capacitor on Condenser #2 is out of its tolerance limit of 6% and recommending replacement. Made sure all connections are tight. Systems are cooling with 20° and 19° temperature splits at this time. Verified systems heat properly. 
Found growth inside of air handler units and growth on unit #2 blower wheel. Quote sent for cleanings and uv system installs. Client accepted quote. 

Recommending soft start kits on both condenser units to bring down the start up amp draw and prolong the life of the compressors. 
Quote sent for soft start kits. 
Quote sent for capacitor replacement. 

Inspected system #2 duct work and syste
Michael A.
Michael A. Checked in
Performed Maitenences on systems. Cleaned/treated drain lines and primary drain pans. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switchs functionality. Checked amp draw on compressors. Compressors are over amping on start up exceeding the factory max LRA amp draw. Checked amp draw on fan motors. Checked capacitors are within factory range. Capacitor on Condenser #2 is out of its tolerance limit of 6% and recommending replacement. Made sure all connections are tight. Systems are cooling with 20° and 19° temperature splits at this time. Verified systems heat properly. Found growth inside of air handler units and growth on unit #2 blower wheel. Quote sent for cleanings and uv system installs. Client accepted quote. Recommending soft start kits on both condenser units to bring down the start up amp draw and prolong the life of the compressors. Quote sent for soft start kits. Quote sent for capacitor replacement. Inspected system #2 duct work and syste
Clearwater, FL 33761
Clearwater, FL - Reprogrammed thermostat to allow heat strip to run with heat pump. Start and test. Unit operating properly at this time.
Justin G.
Justin G. Checked in
Reprogrammed thermostat to allow heat strip to run with heat pump. Start and test. Unit operating properly at this time.
Clearwater, FL 33765

Contact the Bros You Know Today!

Schedule Service Online
servicedetailscustomerreturningschedule
*
Details Regarding Your Request...
Optional: Drag and drop photos and/or videos:
Max. file size: 4 MB.
Your Contact and Service Location...
*
*
*
To Serve You Best...
Have we served you in the past?
Yes
No
*
What Is Convenient For You?
*
What time of day is best for you?
First Available
Morning
Afternoon
*

Call For Same Day Service/Emergencies at 727-217-6148 .

By pressing Submit I agree to receive phone, email, or text messages from Air Bros Air Conditioning & Heating to the provided mobile number and also agree to the Air Bros Air Conditioning & Heating terms and privacy policy. Message & data rates may apply. Consent is not a condition of purchase. We will never share your personal information with third parties for marketing purposes.
Back Next