Upon my inspection, found severely clogged drain line on system #1. Unit was leaking water and the safety float switch was not cutting power to the unit. 
Cleaned and treated drain line and primary drain pan. Had to cut pvc drain line to blow out with nitrogen. Installed serviceable connection joint for future drain cleanings. Installed new safety float switch. Tested operations and system is cooling and draining properly at this time. 
Client signed up for Maitenence agreement. Did not perform full Maitenence's today.
Upon my inspection, found severely clogged drain line on system #1. Unit was leaking water and the safety float switch was not cutting power to the unit. 
Cleaned and treated drain line and primary drain pan. Had to cut pvc drain line to blow out with nitrogen. Installed serviceable connection joint for future drain cleanings. Installed new safety float switch. Tested operations and system is cooling and draining properly at this time. 
Client signed up for Maitenence agreement. Did not perform full Maitenence's today.
Michael A.
Michael A. Checked in
Upon my inspection, found severely clogged drain line on system #1. Unit was leaking water and the safety float switch was not cutting power to the unit. Cleaned and treated drain line and primary drain pan. Had to cut pvc drain line to blow out with nitrogen. Installed serviceable connection joint for future drain cleanings. Installed new safety float switch. Tested operations and system is cooling and draining properly at this time. Client signed up for Maitenence agreement. Did not perform full Maitenence's today.
Safety Harbor, FL 34695
Performed Maitenences on systems. Cleaned/treated drain lines and primary drain pans. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switchs functionality. Checked amp draw on compressors. Checked amp draw on fan motors. Checked capacitors are within factory range. Made sure all connections are tight. Systems are cooling with 20° temperature splits at this time. 
System #2 upstairs deficiencies:
- outdoor copper insulation Degraded and falling apart
- build up on blower wheel
- Growth inside air handler
- Liquid line filter drier inside condenser is rusting/pitted

Client is concerned with humidity and musty smell during the summer time. 
Performed a free duct inspection on both systems: 
Found almost all ducts are not sealed to code. Quote sent for sealing all ducts. 

Scope of work: UV system
- Install New UV system inside upstairs air handler. 
- Clean and sanitize inside air handler excluding the coils and blower wheel
- UV system is transferable to a ne
Performed Maitenences on systems. Cleaned/treated drain lines and primary drain pans. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switchs functionality. Checked amp draw on compressors. Checked amp draw on fan motors. Checked capacitors are within factory range. Made sure all connections are tight. Systems are cooling with 20° temperature splits at this time. 
System #2 upstairs deficiencies:
- outdoor copper insulation Degraded and falling apart
- build up on blower wheel
- Growth inside air handler
- Liquid line filter drier inside condenser is rusting/pitted

Client is concerned with humidity and musty smell during the summer time. 
Performed a free duct inspection on both systems: 
Found almost all ducts are not sealed to code. Quote sent for sealing all ducts. 

Scope of work: UV system
- Install New UV system inside upstairs air handler. 
- Clean and sanitize inside air handler excluding the coils and blower wheel
- UV system is transferable to a ne
Michael A.
Michael A. Checked in
Performed Maitenences on systems. Cleaned/treated drain lines and primary drain pans. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switchs functionality. Checked amp draw on compressors. Checked amp draw on fan motors. Checked capacitors are within factory range. Made sure all connections are tight. Systems are cooling with 20° temperature splits at this time. System #2 upstairs deficiencies: - outdoor copper insulation Degraded and falling apart - build up on blower wheel - Growth inside air handler - Liquid line filter drier inside condenser is rusting/pitted Client is concerned with humidity and musty smell during the summer time. Performed a free duct inspection on both systems: Found almost all ducts are not sealed to code. Quote sent for sealing all ducts. Scope of work: UV system - Install New UV system inside upstairs air handler. - Clean and sanitize inside air handler excluding the coils and blower wheel - UV system is transferable to a ne
Safety Harbor, FL 34695
Reason for call: 
Scheduled repair 

Equipment:
2017 3.5 ton heat pump 
Horizontal in attic 
Concert is ground level on left side of home 

Summary: 
Completed diagnosis to find a restriction on the outdoor txv. The cap tubes were completely frozen. To complete this repair we need to replace the outdoor txv, all refrigerant, and the filter drier. Also informed homeowner of the benefits of the membership program. 

Completed repair on outdoor txv and filter drier. Charged system to specifications. Heating is operating well. There is now an issue with the cooling. Ricky plan to come out to job on Friday morning first thing. 


Homeowner agreed to repair. 
If you received a five star service, please feel inclined to leave a Google review. Thank you for trusting Air Bros with your Hvac needs. Your technician Corbin.
Reason for call: 
Scheduled repair 

Equipment:
2017 3.5 ton heat pump 
Horizontal in attic 
Concert is ground level on left side of home 

Summary: 
Completed diagnosis to find a restriction on the outdoor txv. The cap tubes were completely frozen. To complete this repair we need to replace the outdoor txv, all refrigerant, and the filter drier. Also informed homeowner of the benefits of the membership program. 

Completed repair on outdoor txv and filter drier. Charged system to specifications. Heating is operating well. There is now an issue with the cooling. Ricky plan to come out to job on Friday morning first thing. 


Homeowner agreed to repair. 
If you received a five star service, please feel inclined to leave a Google review. Thank you for trusting Air Bros with your Hvac needs. Your technician Corbin.
Ricky O.
Ricky O. Checked in
Reason for call: Scheduled repair Equipment: 2017 3.5 ton heat pump Horizontal in attic Concert is ground level on left side of home Summary: Completed diagnosis to find a restriction on the outdoor txv. The cap tubes were completely frozen. To complete this repair we need to replace the outdoor txv, all refrigerant, and the filter drier. Also informed homeowner of the benefits of the membership program. Completed repair on outdoor txv and filter drier. Charged system to specifications. Heating is operating well. There is now an issue with the cooling. Ricky plan to come out to job on Friday morning first thing. Homeowner agreed to repair. If you received a five star service, please feel inclined to leave a Google review. Thank you for trusting Air Bros with your Hvac needs. Your technician Corbin.
Safety Harbor, FL 34695
~ 3 Ton 18 SEER High Efficiency Inverter System
~ 10 Year parts warranty 
~ 3 year Labor warranty 
~ 0% 18 month financing
~ $2000 Tax Credit (ends this year)
- Installation of vertical air handler in garage
- Clean and reseal supply plenum
- New thermostat (WiFi compatible)
- New safety float switch
- New insulation on copper
- Installation of Condenser unit
- New Hurricane pad
- New Hurricane straps
- New UV rated insulation on copper
- New filter line dryer
100% satisfaction
Quote is eligible for 30 days
~ 3 Ton 18 SEER High Efficiency Inverter System
~ 10 Year parts warranty 
~ 3 year Labor warranty 
~ 0% 18 month financing
~ $2000 Tax Credit (ends this year)
- Installation of vertical air handler in garage
- Clean and reseal supply plenum
- New thermostat (WiFi compatible)
- New safety float switch
- New insulation on copper
- Installation of Condenser unit
- New Hurricane pad
- New Hurricane straps
- New UV rated insulation on copper
- New filter line dryer
100% satisfaction
Quote is eligible for 30 days
Kyle K.
Kyle K. Checked in
~ 3 Ton 18 SEER High Efficiency Inverter System ~ 10 Year parts warranty ~ 3 year Labor warranty ~ 0% 18 month financing ~ $2000 Tax Credit (ends this year) - Installation of vertical air handler in garage - Clean and reseal supply plenum - New thermostat (WiFi compatible) - New safety float switch - New insulation on copper - Installation of Condenser unit - New Hurricane pad - New Hurricane straps - New UV rated insulation on copper - New filter line dryer 100% satisfaction Quote is eligible for 30 days
Safety Harbor, FL 34695
Diagnosed bad thermostat. Replacing with recover thermostat 1 year warranty. Verified heating and cooling functions. Found broken uv light system in air handler with visible growth. Quote sent to replace and clean UV system.
Diagnosed bad thermostat. Replacing with recover thermostat 1 year warranty. Verified heating and cooling functions. Found broken uv light system in air handler with visible growth. Quote sent to replace and clean UV system.
Michael A.
Michael A. Checked in
Diagnosed bad thermostat. Replacing with recover thermostat 1 year warranty. Verified heating and cooling functions. Found broken uv light system in air handler with visible growth. Quote sent to replace and clean UV system.
Safety Harbor, FL 34695
Performed Maitenence on system. Cleaned/treated drain line and primary drain pan. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switch functionality. Checked amp draw on compressor. Checked amp draw on fan motor. Checked capacitor is within factory range. made sure all connections are tight. System is cooling with a 20° temperature split at this time. 
Recommending a bi annual Maitenence membership. 
Drain line was very clogged.
Performed Maitenence on system. Cleaned/treated drain line and primary drain pan. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switch functionality. Checked amp draw on compressor. Checked amp draw on fan motor. Checked capacitor is within factory range. made sure all connections are tight. System is cooling with a 20° temperature split at this time. 
Recommending a bi annual Maitenence membership. 
Drain line was very clogged.
Michael A.
Michael A. Checked in
Performed Maitenence on system. Cleaned/treated drain line and primary drain pan. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switch functionality. Checked amp draw on compressor. Checked amp draw on fan motor. Checked capacitor is within factory range. made sure all connections are tight. System is cooling with a 20° temperature split at this time. Recommending a bi annual Maitenence membership. Drain line was very clogged.
Safety Harbor, FL 34695
Performed two Maitenences on systems. Cleaned/treated drain lines and primary drain pans. Cleaned condenser coils. Evaporator coils are clean on upstairs unit, downstairs unit are dirty but do not recommend cleaning 23 year old coils. Verified safety float switch functionality. Checked amp draw on compressor. Compressor start up amp draw on both systems are over amping. Installed hard start kit on upstairs system to drop amp draw of 92 to 64 with a max rating on the system of 83. Explained to client that this is a bandaid on a failing compressor. Checked amp draw on fan motor. Checked capacitors are within factory range. made sure all connections are tight. Systems are cooling with 20° temperature splits at this time.
Performed two Maitenences on systems. Cleaned/treated drain lines and primary drain pans. Cleaned condenser coils. Evaporator coils are clean on upstairs unit, downstairs unit are dirty but do not recommend cleaning 23 year old coils. Verified safety float switch functionality. Checked amp draw on compressor. Compressor start up amp draw on both systems are over amping. Installed hard start kit on upstairs system to drop amp draw of 92 to 64 with a max rating on the system of 83. Explained to client that this is a bandaid on a failing compressor. Checked amp draw on fan motor. Checked capacitors are within factory range. made sure all connections are tight. Systems are cooling with 20° temperature splits at this time.
Michael A.
Michael A. Checked in
Performed two Maitenences on systems. Cleaned/treated drain lines and primary drain pans. Cleaned condenser coils. Evaporator coils are clean on upstairs unit, downstairs unit are dirty but do not recommend cleaning 23 year old coils. Verified safety float switch functionality. Checked amp draw on compressor. Compressor start up amp draw on both systems are over amping. Installed hard start kit on upstairs system to drop amp draw of 92 to 64 with a max rating on the system of 83. Explained to client that this is a bandaid on a failing compressor. Checked amp draw on fan motor. Checked capacitors are within factory range. made sure all connections are tight. Systems are cooling with 20° temperature splits at this time.
Safety Harbor, FL 34695
Safety Harbor, FL - Replace Wiring from Panel to Disconnect box
Griffin K.
Griffin K. Checked in
Replace Wiring from Panel to Disconnect box
Safety Harbor, FL 34695
Upon my inspection, found system had 27 psi of refrigerant. Performed leak search and found leak. Repaired leak on copper refrigerant line inside condenser unit that connects to the pressure switch. Cleaned condenser coils. Strapped up loose wires inside the condenser. Installed/welded on new liquid line filter dryer. Put system under a vacuum and charged system with 8lbs of virgin 410a refrigerant. Achieved a 20° temperature split and a 13° subcool. System is cooling properly at this time. 

Included 2lbs refrigerant complimentary. 
Cleaned condenser coils complimentary
Upon my inspection, found system had 27 psi of refrigerant. Performed leak search and found leak. Repaired leak on copper refrigerant line inside condenser unit that connects to the pressure switch. Cleaned condenser coils. Strapped up loose wires inside the condenser. Installed/welded on new liquid line filter dryer. Put system under a vacuum and charged system with 8lbs of virgin 410a refrigerant. Achieved a 20° temperature split and a 13° subcool. System is cooling properly at this time. 

Included 2lbs refrigerant complimentary. 
Cleaned condenser coils complimentary
Michael A.
Michael A. Checked in
Upon my inspection, found system had 27 psi of refrigerant. Performed leak search and found leak. Repaired leak on copper refrigerant line inside condenser unit that connects to the pressure switch. Cleaned condenser coils. Strapped up loose wires inside the condenser. Installed/welded on new liquid line filter dryer. Put system under a vacuum and charged system with 8lbs of virgin 410a refrigerant. Achieved a 20° temperature split and a 13° subcool. System is cooling properly at this time. Included 2lbs refrigerant complimentary. Cleaned condenser coils complimentary
Safety Harbor, FL 34695
Griffin K.
Griffin K. Checked in
Replaced low voltage fuse observed unit running for 15 min no other issues occurred
Safety Harbor, FL 34695
Justin G.
Justin G. Checked in
New drain. New primary float switch New media filter 4” for Rheem 17”. Level unit. Tax and labor.
Safety Harbor, FL 34695
Justin G.
Justin G. Checked in
On arrival found unit running and cooling. Pan is dry below unit and unit draining. Found primary float not installed properly. Recommend to replace drain and float. Check level on unit. Made client aware other issues are possible once we have unit draining properly.
Safety Harbor, FL 34695
Michael A.
Michael A. Checked in
Upon arrival, I found condenser unit was not operating properly. Further diagnosis indicated a failed capacitor. Replaced capacitor and system started up. Amp draw on fan motor is high and over its rated limit (reading .8 and max rating is 6). Client was recommended to clean condenser coils but will perform work themselves. Client was also notified that the condenser fan motor is showing signs of wear and will possibly fail in the near future. System is now cooling with a 20° split.
Safety Harbor, FL 34695
- 3 Ton 15 SEER heat pump system replacement. 
- 0% financing 18 months
- Replacement of horizontal air handler
- Replacement of new condenser and hurricane pad
- New UV insulation
- Flush lineset
- New drain pan and safety switches
- New drain line connections to unit. (Remove old p trap and install new because it is leaking condensation. 
- New thermostat
- New liquid line filter line dryer
- 3 Ton 15 SEER heat pump system replacement. 
- 0% financing 18 months
- Replacement of horizontal air handler
- Replacement of new condenser and hurricane pad
- New UV insulation
- Flush lineset
- New drain pan and safety switches
- New drain line connections to unit. (Remove old p trap and install new because it is leaking condensation. 
- New thermostat
- New liquid line filter line dryer
Kyle K.
Kyle K. Checked in
- 3 Ton 15 SEER heat pump system replacement. - 0% financing 18 months - Replacement of horizontal air handler - Replacement of new condenser and hurricane pad - New UV insulation - Flush lineset - New drain pan and safety switches - New drain line connections to unit. (Remove old p trap and install new because it is leaking condensation. - New thermostat - New liquid line filter line dryer
Safety Harbor, FL 34695
Justin G.
Justin G. Checked in
On arrival found unit not cooling due to weak capacitor and bad outdoor fan motor. Replaced parts. Start and test. Pressures good. Temp split good. Performed maintenance on system. Unit cooling properly at this time.
Safety Harbor, FL 34695
Ricky O.
Ricky O. Checked in
Blown fuse. Replaced fuse. No shorts found. Told client to monitor. I’m Maint plan
Safety Harbor, FL 34695
Safety Harbor, FL - On arrival found condenser tripping breaker due to loose wire connections in panel. Tightened connection. Start and test. Breaker staying cool to touch. Pressures good. Temp split good. Unit cooling properly at this time.
Justin G.
Justin G. Checked in
On arrival found condenser tripping breaker due to loose wire connections in panel. Tightened connection. Start and test. Breaker staying cool to touch. Pressures good. Temp split good. Unit cooling properly at this time.
Safety Harbor, FL 34695
no cool
Upon arrival, thermostat works and air handler is running no activity from condensing unit
Found condenser locked out on high-pressure
Found that fan side of capacitor is dead reading .09 out of 5 µF.
Replaced 35+5 µF capacitor and restarted system and cooling
Checked refrigerant pressure system is back up and running at this time
no cool
Upon arrival, thermostat works and air handler is running no activity from condensing unit
Found condenser locked out on high-pressure
Found that fan side of capacitor is dead reading .09 out of 5 µF.
Replaced 35+5 µF capacitor and restarted system and cooling
Checked refrigerant pressure system is back up and running at this time
Sha’nya B.
Sha’nya B. Checked in
no cool Upon arrival, thermostat works and air handler is running no activity from condensing unit Found condenser locked out on high-pressure Found that fan side of capacitor is dead reading .09 out of 5 µF. Replaced 35+5 µF capacitor and restarted system and cooling Checked refrigerant pressure system is back up and running at this time
Safety Harbor, FL 34695
Ricky O.
Ricky O. Checked in
Furnish and install the following 3.5 ton 15.2 SEER2 Ruud heat pump 2-stage split system with 5kw heater Hurricane pad Anchor condenser Re-use media filter Re-use Reme-halo Primary float switch Remove existing equipment Connect to existing ducts and electric Seal unit to code Pull disconnect heater Uv rated insulation for outdoor copper Complimentary duct sanitation for both systems Tax labor and permit included 10 year parts warranty 3 year labor warranty
Safety Harbor, FL 34695
Justin G.
Justin G. Checked in
Replace evaporator txv and filter dryer. Pressure test line set. Pull vacuum on system. Weigh in 10 lbs of refrigerant. Start and test.
Safety Harbor, FL 34695
Justin G.
Justin G. Checked in
On arrival found upstairs unit empty on refrigerant. Performed leak search and found indoor txv leaking. Will return to replace part later. Unit is not cooling at this time.
Safety Harbor, FL 34695

Contact the Bros You Know Today!

Schedule Service Online
servicedetailscustomerreturningschedule
*
Details Regarding Your Request...
Optional: Drag and drop photos and/or videos:
Max. file size: 4 MB.
Your Contact and Service Location...
*
*
*
To Serve You Best...
Have we served you in the past?
Yes
No
*
What Is Convenient For You?
*
What time of day is best for you?
First Available
Morning
Afternoon
*

Call For Same Day Service/Emergencies at 727-217-6148 .

By pressing Submit I agree to receive phone, email, or text messages from Air Bros Air Conditioning & Heating to the provided mobile number and also agree to the Air Bros Air Conditioning & Heating terms and privacy policy. Message & data rates may apply. Consent is not a condition of purchase. We will never share your personal information with third parties for marketing purposes.
Back Next