Instant Quote Shop Filters Call Air Bros

Tarpon Springs, FL

air-bros-team-with-truck

Expert Cooling, Heating and Electrical In Tarpon Springs, FL

Air Bros is proud to provide expert cooling, heating, indoor air quality and electrical services in Tarpon Springs, FL. With 24 hour availability and licensed and trained technicians on call, you can trust our impeccable work from start to finish.

We invite you to read our reviews below and find out why your neighbors consider us to be their nearby heating and air company and local electrician in Tarpon Springs, FL.

Recent Jobs and Reviews in Tarpon Springs, FL

Tarpon Springs, FL at a glance

Air Bros Air Conditioning & Electrical has completed 10 jobs in Tarpon Springs, FL between June 2025 and September 2026.

The most recent job was on September 2, 2026.

Job Locations and Reviews

5 Ton 15.2 SEER Heat Pump 2 stage cooling RUUD system 
~ 10 Year parts warranty  
~ 3 year Labor warranty
** Cash price (5% off)= $10,925**
______
- Installation of Horizontal air handler in attic
- New secondary safety pan
- Seal plenums to unit
- 5 kw back up heat element
- Program existing thermostat 
- New safety float switches
- New insulation on copper
- Strap up drain line for proper pitch
- Replace breakers as needed
- Flush and test existing condensate drain line
- Seal one supply duct to supply plenum (existing duct)
______
- Installation of Condenser unit 
- Flush existing refrigerant lines
- Replace breakers as needed
- New 4” hurricane concrete pad
- New Hurricane straps 
- New UV rated insulation on copper
- New filter line dryer
- Refrigerant locking caps
- Vacuum system to 500 microns
- Charge system with refrigerant to proper pressures

- Completed to code
100% satisfaction
5 Ton 15.2 SEER Heat Pump 2 stage cooling RUUD system 
~ 10 Year parts warranty  
~ 3 year Labor warranty
** Cash price (5% off)= $10,925**
______
- Installation of Horizontal air handler in attic
- New secondary safety pan
- Seal plenums to unit
- 5 kw back up heat element
- Program existing thermostat 
- New safety float switches
- New insulation on copper
- Strap up drain line for proper pitch
- Replace breakers as needed
- Flush and test existing condensate drain line
- Seal one supply duct to supply plenum (existing duct)
______
- Installation of Condenser unit 
- Flush existing refrigerant lines
- Replace breakers as needed
- New 4” hurricane concrete pad
- New Hurricane straps 
- New UV rated insulation on copper
- New filter line dryer
- Refrigerant locking caps
- Vacuum system to 500 microns
- Charge system with refrigerant to proper pressures

- Completed to code
100% satisfaction
Kyle K.
Kyle K. Checked in
5 Ton 15.2 SEER Heat Pump 2 stage cooling RUUD system ~ 10 Year parts warranty ~ 3 year Labor warranty ** Cash price (5% off)= $10,925** ______ - Installation of Horizontal air handler in attic - New secondary safety pan - Seal plenums to unit - 5 kw back up heat element - Program existing thermostat - New safety float switches - New insulation on copper - Strap up drain line for proper pitch - Replace breakers as needed - Flush and test existing condensate drain line - Seal one supply duct to supply plenum (existing duct) ______ - Installation of Condenser unit - Flush existing refrigerant lines - Replace breakers as needed - New 4” hurricane concrete pad - New Hurricane straps - New UV rated insulation on copper - New filter line dryer - Refrigerant locking caps - Vacuum system to 500 microns - Charge system with refrigerant to proper pressures - Completed to code 100% satisfaction
Tarpon Springs, FL 34688
System #1:
Client states system has always has water issues. 
Upon my inspection, found system cooling with a poor 13° temperature split. 
Evaporator coils are severely corroded and dirty. 
Air filters in 3 bedrooms are severely dirty. 
Primary drain pan is blocked up with gunk. 
Blower speed is set to the highest setting. 
System pressures indicate very low on refrigerant
Found refrigerant leak at the condenser suction line connection. 

All of these issues combined are causing water issues and cooling issues. 

System as a whole is in poor condition. 
Providing quotes for repairs with no guarantee and for full system replacement with warranties. 

Client also has concerns with the laundry room not getting adequate air flow. We will need to address this issue upon completion of repairs or full system replacement.
System #1:
Client states system has always has water issues. 
Upon my inspection, found system cooling with a poor 13° temperature split. 
Evaporator coils are severely corroded and dirty. 
Air filters in 3 bedrooms are severely dirty. 
Primary drain pan is blocked up with gunk. 
Blower speed is set to the highest setting. 
System pressures indicate very low on refrigerant
Found refrigerant leak at the condenser suction line connection. 

All of these issues combined are causing water issues and cooling issues. 

System as a whole is in poor condition. 
Providing quotes for repairs with no guarantee and for full system replacement with warranties. 

Client also has concerns with the laundry room not getting adequate air flow. We will need to address this issue upon completion of repairs or full system replacement.
Michael A.
Michael A. Checked in
System #1: Client states system has always has water issues. Upon my inspection, found system cooling with a poor 13° temperature split. Evaporator coils are severely corroded and dirty. Air filters in 3 bedrooms are severely dirty. Primary drain pan is blocked up with gunk. Blower speed is set to the highest setting. System pressures indicate very low on refrigerant Found refrigerant leak at the condenser suction line connection. All of these issues combined are causing water issues and cooling issues. System as a whole is in poor condition. Providing quotes for repairs with no guarantee and for full system replacement with warranties. Client also has concerns with the laundry room not getting adequate air flow. We will need to address this issue upon completion of repairs or full system replacement.
Tarpon Springs, FL 34688
Reason for call:
No cool 

Equipment:
2015 3 ton Goodman 
Vertical in garage 
Condenser on left side of home 

Summary:
Found compressor dead on arrival confirmed proper voltage to compressor, confirmed proper readings at capacitor. Tried to wire in hard start kit. Compressor still failed to start up. 

Solution:
Recommended system replacement due to compressor being a very expensive repair outside of warranty.
Reason for call:
No cool 

Equipment:
2015 3 ton Goodman 
Vertical in garage 
Condenser on left side of home 

Summary:
Found compressor dead on arrival confirmed proper voltage to compressor, confirmed proper readings at capacitor. Tried to wire in hard start kit. Compressor still failed to start up. 

Solution:
Recommended system replacement due to compressor being a very expensive repair outside of warranty.
Corbin C.
Corbin C. Checked in
Reason for call: No cool Equipment: 2015 3 ton Goodman Vertical in garage Condenser on left side of home Summary: Found compressor dead on arrival confirmed proper voltage to compressor, confirmed proper readings at capacitor. Tried to wire in hard start kit. Compressor still failed to start up. Solution: Recommended system replacement due to compressor being a very expensive repair outside of warranty.
Tarpon Springs, FL 34689
Found water and safety switch and extreme growth inside drain line flushed and clean drain line put drain solution in pan and drain line left tablets and pan to prevent backup in the future. Confirmed proper operation of equipment in all aspects.
Found water and safety switch and extreme growth inside drain line flushed and clean drain line put drain solution in pan and drain line left tablets and pan to prevent backup in the future. Confirmed proper operation of equipment in all aspects.
Corbin C.
Corbin C. Checked in
Found water and safety switch and extreme growth inside drain line flushed and clean drain line put drain solution in pan and drain line left tablets and pan to prevent backup in the future. Confirmed proper operation of equipment in all aspects.
Tarpon Springs, FL 34689
Reason for call:
Second opinion

Summary:
There were no issues at the System the float switch wasn't pitched properly adjusted pitch did full inspection. operation of equipment is phenomenal. Changed all filters inside home built value with client. Client signed up on membership.
Reason for call:
Second opinion

Summary:
There were no issues at the System the float switch wasn't pitched properly adjusted pitch did full inspection. operation of equipment is phenomenal. Changed all filters inside home built value with client. Client signed up on membership.
Corbin C.
Corbin C. Checked in
Reason for call: Second opinion Summary: There were no issues at the System the float switch wasn't pitched properly adjusted pitch did full inspection. operation of equipment is phenomenal. Changed all filters inside home built value with client. Client signed up on membership.
Tarpon Springs, FL 34689
Reason for call:
No cool

Equipment:
2016 trane 2.5 ton 
Vertical in front closet 
Condenser on right side of home 

Summary: 
On arrival found drain line clogged and thermostat shut off. Confirmed proper operation of equipment. 20 degree split. Proper amp draws. Proper cap readings. 

Solution:
Flushed drain line and proper drainage was restored.
Reason for call:
No cool

Equipment:
2016 trane 2.5 ton 
Vertical in front closet 
Condenser on right side of home 

Summary: 
On arrival found drain line clogged and thermostat shut off. Confirmed proper operation of equipment. 20 degree split. Proper amp draws. Proper cap readings. 

Solution:
Flushed drain line and proper drainage was restored.
Corbin C.
Corbin C. Checked in
Reason for call: No cool Equipment: 2016 trane 2.5 ton Vertical in front closet Condenser on right side of home Summary: On arrival found drain line clogged and thermostat shut off. Confirmed proper operation of equipment. 20 degree split. Proper amp draws. Proper cap readings. Solution: Flushed drain line and proper drainage was restored.
Tarpon Springs, FL 34689
Michael A.
Michael A. Checked in
Find My inspection, found upstairs system is 20 years old and has a bad capacitor and low on refrigerant. Replaced capacitor and added 3 pounds of refrigerant. System had a 10° split and now has a 16 to 18° temperature split. Pressures after adding refrigerant are now indicating that there might be a metering device issue. Let the tenant know since the tenant was paying for the repairs today that the system is not in great condition and to not expect a whole lot out of it. Client needs to change filters asap. System is cooling the best it can at this time.
Tarpon Springs, FL 34689
Reason for call:
No cool

Equipment:
2019 grand aire 3.5 ton heat pump
Horizontal in garage 12-15ft elevated 
Condenser on platform right of home 

Summary:
On arrival found failed blower motor and frozen evaporator and frozen suction. Confirmed motor had power and call for fan. Confirmed cap readings, uv treatment is install. 

Solution 
Replace air handler blower motor 
Add transformer to uv treatment 

Restored operation to equipment signed homeowner up on membership plan.
Reason for call:
No cool

Equipment:
2019 grand aire 3.5 ton heat pump
Horizontal in garage 12-15ft elevated 
Condenser on platform right of home 

Summary:
On arrival found failed blower motor and frozen evaporator and frozen suction. Confirmed motor had power and call for fan. Confirmed cap readings, uv treatment is install. 

Solution 
Replace air handler blower motor 
Add transformer to uv treatment 

Restored operation to equipment signed homeowner up on membership plan.
Corbin C.
Corbin C. Checked in
Reason for call: No cool Equipment: 2019 grand aire 3.5 ton heat pump Horizontal in garage 12-15ft elevated Condenser on platform right of home Summary: On arrival found failed blower motor and frozen evaporator and frozen suction. Confirmed motor had power and call for fan. Confirmed cap readings, uv treatment is install. Solution Replace air handler blower motor Add transformer to uv treatment Restored operation to equipment signed homeowner up on membership plan.
Tarpon Springs, FL 34689
Tenant states system does not cool well during the day, Thermostat is hard to function, and filter does not stay in. 
Upon my inspection, found system is cooling with only a 12° temperature split. Evaporator coils are very dirty. The filter access is not easy to use. Checked pressures and found that the system has a restriction on the TXV. Client is aware that evaporator coil is at risk of freezing due to low saturation temperature. 
Air handler is a 2003 and condenser is a 2024. It is likely that the condenser was only replaced because of the hurricane damage. Systems are not matching. 

Will provide quote for TXV replacement if it is available. 
Providing quote and highly recommending full system replacement
Tenant states system does not cool well during the day, Thermostat is hard to function, and filter does not stay in. 
Upon my inspection, found system is cooling with only a 12° temperature split. Evaporator coils are very dirty. The filter access is not easy to use. Checked pressures and found that the system has a restriction on the TXV. Client is aware that evaporator coil is at risk of freezing due to low saturation temperature. 
Air handler is a 2003 and condenser is a 2024. It is likely that the condenser was only replaced because of the hurricane damage. Systems are not matching. 

Will provide quote for TXV replacement if it is available. 
Providing quote and highly recommending full system replacement
Michael A.
Michael A. Checked in
Tenant states system does not cool well during the day, Thermostat is hard to function, and filter does not stay in. Upon my inspection, found system is cooling with only a 12° temperature split. Evaporator coils are very dirty. The filter access is not easy to use. Checked pressures and found that the system has a restriction on the TXV. Client is aware that evaporator coil is at risk of freezing due to low saturation temperature. Air handler is a 2003 and condenser is a 2024. It is likely that the condenser was only replaced because of the hurricane damage. Systems are not matching. Will provide quote for TXV replacement if it is available. Providing quote and highly recommending full system replacement
Tarpon Springs, FL 34689
noise complaint
Upon arrival, homeowner explained that they just noticed this morning that when the condensing unit turned on, it made a very loud noise. Upon initial inspection when condenser started I did hear that it was loud but not unusual. In rush amp draw measured 64 out of total allowed 124 A. 
Found system was low on refrigerant. Recommended leak search. Homeowner declined and just wants to add refrigerant at this time. Added 2 pounds of R410 a to the system. Advised homeowner to keep an eye on how everything is running over the next month or so as there is no way to know how fast or slow slowly, the refrigerant will leak out again.
signed up for maintenance membership
noise complaint
Upon arrival, homeowner explained that they just noticed this morning that when the condensing unit turned on, it made a very loud noise. Upon initial inspection when condenser started I did hear that it was loud but not unusual. In rush amp draw measured 64 out of total allowed 124 A. 
Found system was low on refrigerant. Recommended leak search. Homeowner declined and just wants to add refrigerant at this time. Added 2 pounds of R410 a to the system. Advised homeowner to keep an eye on how everything is running over the next month or so as there is no way to know how fast or slow slowly, the refrigerant will leak out again.
signed up for maintenance membership
Sha’nya B.
Sha’nya B. Checked in
noise complaint Upon arrival, homeowner explained that they just noticed this morning that when the condensing unit turned on, it made a very loud noise. Upon initial inspection when condenser started I did hear that it was loud but not unusual. In rush amp draw measured 64 out of total allowed 124 A. Found system was low on refrigerant. Recommended leak search. Homeowner declined and just wants to add refrigerant at this time. Added 2 pounds of R410 a to the system. Advised homeowner to keep an eye on how everything is running over the next month or so as there is no way to know how fast or slow slowly, the refrigerant will leak out again. signed up for maintenance membership
Tarpon Springs, FL 34689

Contact the Bros You Know Today!

Gravity Forms Pagination Must be Steps