Reason for call:
No cool

Equipment:
2019 grand aire 3.5 ton heat pump
Horizontal in garage 12-15ft elevated 
Condenser on platform right of home 

Summary:
On arrival found failed blower motor and frozen evaporator and frozen suction. Confirmed motor had power and call for fan. Confirmed cap readings, uv treatment is install. 

Solution 
Replace air handler blower motor 
Add transformer to uv treatment 

Restored operation to equipment signed homeowner up on membership plan.
Reason for call:
No cool

Equipment:
2019 grand aire 3.5 ton heat pump
Horizontal in garage 12-15ft elevated 
Condenser on platform right of home 

Summary:
On arrival found failed blower motor and frozen evaporator and frozen suction. Confirmed motor had power and call for fan. Confirmed cap readings, uv treatment is install. 

Solution 
Replace air handler blower motor 
Add transformer to uv treatment 

Restored operation to equipment signed homeowner up on membership plan.
Corbin C.
Corbin C. Checked in
Reason for call: No cool Equipment: 2019 grand aire 3.5 ton heat pump Horizontal in garage 12-15ft elevated Condenser on platform right of home Summary: On arrival found failed blower motor and frozen evaporator and frozen suction. Confirmed motor had power and call for fan. Confirmed cap readings, uv treatment is install. Solution Replace air handler blower motor Add transformer to uv treatment Restored operation to equipment signed homeowner up on membership plan.
Tarpon Springs, FL 34689
Tenant states system does not cool well during the day, Thermostat is hard to function, and filter does not stay in. 
Upon my inspection, found system is cooling with only a 12° temperature split. Evaporator coils are very dirty. The filter access is not easy to use. Checked pressures and found that the system has a restriction on the TXV. Client is aware that evaporator coil is at risk of freezing due to low saturation temperature. 
Air handler is a 2003 and condenser is a 2024. It is likely that the condenser was only replaced because of the hurricane damage. Systems are not matching. 

Will provide quote for TXV replacement if it is available. 
Providing quote and highly recommending full system replacement
Tenant states system does not cool well during the day, Thermostat is hard to function, and filter does not stay in. 
Upon my inspection, found system is cooling with only a 12° temperature split. Evaporator coils are very dirty. The filter access is not easy to use. Checked pressures and found that the system has a restriction on the TXV. Client is aware that evaporator coil is at risk of freezing due to low saturation temperature. 
Air handler is a 2003 and condenser is a 2024. It is likely that the condenser was only replaced because of the hurricane damage. Systems are not matching. 

Will provide quote for TXV replacement if it is available. 
Providing quote and highly recommending full system replacement
Michael A.
Michael A. Checked in
Tenant states system does not cool well during the day, Thermostat is hard to function, and filter does not stay in. Upon my inspection, found system is cooling with only a 12° temperature split. Evaporator coils are very dirty. The filter access is not easy to use. Checked pressures and found that the system has a restriction on the TXV. Client is aware that evaporator coil is at risk of freezing due to low saturation temperature. Air handler is a 2003 and condenser is a 2024. It is likely that the condenser was only replaced because of the hurricane damage. Systems are not matching. Will provide quote for TXV replacement if it is available. Providing quote and highly recommending full system replacement
Tarpon Springs, FL 34689
noise complaint
Upon arrival, homeowner explained that they just noticed this morning that when the condensing unit turned on, it made a very loud noise. Upon initial inspection when condenser started I did hear that it was loud but not unusual. In rush amp draw measured 64 out of total allowed 124 A. 
Found system was low on refrigerant. Recommended leak search. Homeowner declined and just wants to add refrigerant at this time. Added 2 pounds of R410 a to the system. Advised homeowner to keep an eye on how everything is running over the next month or so as there is no way to know how fast or slow slowly, the refrigerant will leak out again.
signed up for maintenance membership
noise complaint
Upon arrival, homeowner explained that they just noticed this morning that when the condensing unit turned on, it made a very loud noise. Upon initial inspection when condenser started I did hear that it was loud but not unusual. In rush amp draw measured 64 out of total allowed 124 A. 
Found system was low on refrigerant. Recommended leak search. Homeowner declined and just wants to add refrigerant at this time. Added 2 pounds of R410 a to the system. Advised homeowner to keep an eye on how everything is running over the next month or so as there is no way to know how fast or slow slowly, the refrigerant will leak out again.
signed up for maintenance membership
Sha’nya B.
Sha’nya B. Checked in
noise complaint Upon arrival, homeowner explained that they just noticed this morning that when the condensing unit turned on, it made a very loud noise. Upon initial inspection when condenser started I did hear that it was loud but not unusual. In rush amp draw measured 64 out of total allowed 124 A. Found system was low on refrigerant. Recommended leak search. Homeowner declined and just wants to add refrigerant at this time. Added 2 pounds of R410 a to the system. Advised homeowner to keep an eye on how everything is running over the next month or so as there is no way to know how fast or slow slowly, the refrigerant will leak out again. signed up for maintenance membership
Tarpon Springs, FL 34689

Contact the Bros You Know Today!

Schedule Service Online
servicedetailscustomerreturningschedule
*
Details Regarding Your Request...
Optional: Drag and drop photos and/or videos:
Max. file size: 4 MB.
Your Contact and Service Location...
*
*
*
To Serve You Best...
Have we served you in the past?
Yes
No
*
What Is Convenient For You?
*
What time of day is best for you?
First Available
Morning
Afternoon
*

Call For Same Day Service/Emergencies at 727-217-6148 .

By pressing Submit I agree to receive phone, email, or text messages from Air Bros Air Conditioning & Heating to the provided mobile number and also agree to the Air Bros Air Conditioning & Heating terms and privacy policy. Message & data rates may apply. Consent is not a condition of purchase. We will never share your personal information with third parties for marketing purposes.
Back Next