The Best AC Repair in St. Petersburg, FL — From Technicians Your Neighbors Already Trust

When your AC quits in the middle of a St. Pete summer, you don't want a stranger in an unmarked van. You want a technician your neighbors already know and trust. Air Bros Air Conditioning & Electrical has been fixing air conditioners in St. Petersburg since 2020, but our roots run deeper — founder Ricky Orta grew up learning the trade from his father and has been a licensed HVAC contractor since 2006. That local, hands-on experience is why homeowners from Historic Kenwood to Snell Isle call us the best AC repair company in St. Petersburg.

We're headquartered right here in the Shore Acres neighborhood, so when you call, you're not routed to a call center — you're talking to the same local team that services your street.

Call us at 727-217-6148 or contact us online today for all of your HVAC, indoor air quality and electrical needs.

Meet the technicians who service St. Petersburg

What to expect when we show up

Calling a repair company you've never used before shouldn't feel like a gamble. Here's exactly how an Air Bros service call goes, every time.

You'll get a heads-up before we arrive, then a uniformed technician in a marked Air Bros vehicle shows up in the window we promised. We diagnose the whole system — not just the obvious symptom — then explain what we found and what your options are before any work starts. You approve the price up front, we make the repair, and we don't leave until we've confirmed the system is cooling the way it should.

Every technician is a background-checked, drug-tested Air Bros employee — never a subcontractor — and each one is trained to service every major AC and heat pump brand. It's the kind of consistency you can only get from a local team that answers to its own name.

And if something isn't right? Our 100% satisfaction guarantee means we make it right.

Signs you need AC repair

St. Petersburg's heat and humidity push air conditioners harder than almost anywhere else in the country. Call for AC repair if you notice:

  • Warm air blowing from vents, or the system running constantly without cooling
  • Water pooling around your air handler (a common issue in St. Pete's older homes with attic-run drain lines)
  • Musty odors or visible mold near vents — a sign of a clogged condensate line or dirty coil
  • Rising humidity indoors despite the AC running
  • Short cycling, tripped breakers, or a system that won't turn on at all

Our technicians diagnose the full system on every call — refrigerant charge, temperature split, electrical connections, and drain line — so you get a real fix, not a temporary patch.

Comprehensive HVAC Services in St. Petersburg

We offer a full range of heating and cooling services to keep your St. Petersburg, FL, home comfortable year-round:

  • Air Conditioning: From AC repair and AC installation to routine maintenance, we ensure your cooling system keeps you comfortable during those hot Florida summers. We offer same-day service for AC emergencies, so you never have to suffer in the heat.
  • Heating: Stay warm and cozy in the winter with our comprehensive heating services. We repair and install all types of heating systems, including furnaces and heat pumps, and offer preventative maintenance to keep your system running efficiently.
  • Indoor Air Quality: Improve your indoor air quality with our dehumidifier and UV light installation services. We'll help you control excess humidity and eliminate airborne contaminants, creating a healthier home environment.
  • Ductwork: Ensure optimal airflow and energy efficiency with our ductwork repair and installation services. We can address leaks and damage, and design a system that's perfect for your home.
  • Pool Heater Services: Extend your swim season with our pool heater installation and repair services.
  • Electrical Services: From outlet and switch replacements to ceiling fan installations to whole-house surge protector installations, we have the experts to handle your electrical service needs.

Our experienced technicians are skilled in all aspects of HVAC service and are dedicated to providing top-quality workmanship and customer care.

Why Choose Air Bros?

  • Local Expertise: We understand the unique climate challenges of St. Petersburg.
  • Fast and Reliable Service: We offer same-day service for AC emergencies and prioritize prompt service for all your HVAC needs.
  • Experienced Technicians: Our team is highly trained and experienced in all aspects of HVAC service.
  • Upfront Pricing: We provide transparent pricing with no hidden costs.
  • Customer Satisfaction Guaranteed: Your comfort and satisfaction are our top priorities.

Contact Air Bros Today!

Whether you need emergency AC repair, a new heating system installation, or any other HVAC service, Air Bros is here to help. Contact us today for a free consultation or to schedule a service appointment. We're proud to be your trusted HVAC partner in St. Petersburg!

Call us at 727-217-6148 or contact us online today!

Recent Jobs and Reviews in St. Petersburg, FL

St. Petersburg, FL at a glance

Air Bros Air Conditioning & Electrical has completed 25 jobs in St. Petersburg, FL between May 2026 and June 2026.

The most recent job was on June 1, 2026.

Air Bros Air Conditioning & Electrical has completed 1,919 jobs in St. Petersburg, FL in the last 12 months. The first job there was in December 2024.

Job Locations and Reviews

Corbin C.
Corbin C. Checked in
Reason for call: No cool Equipment: 21 year old American standard Summary: On arrival had no power at condenser. Talked with homeowner to find he had been messing inside the air handler with a uv bulb. Found common connection loose in bundle at air handler. Tighten wire nut and outdoor unit kicked on confirmed proper temps, proper pressure. Homeowner had unit revamped last year with new starting components. Solution: Homeowner did not want quotes due to a construction job he has planned will increase house by 300-500 sq ft. He will call for qoutinv once he figures that out.
St. Petersburg, FL 33713
Upon arrival, I found that the condenser was not receiving power. I traced the low-voltage circuit and determined that the issue originated at the float switch. Although the float switch was not actively triggered, it was interrupting power to the condenser. I replaced the faulty float switch, restored power, and verified proper system operation.

At this time, the system is functioning normally. However, I recommend scheduling a preventive maintenance service, as the system is due for a full inspection and cleaning. Routine maintenance helps improve efficiency, extend equipment life, and reduce the likelihood of unexpected breakdowns.

Our maintenance membership program can help save money over time and includes additional benefits such as free service calls and 10% off parts and labor.

If you have any questions or concerns, please don’t hesitate to reach out. Thank you for your business, and have a great day.
Upon arrival, I found that the condenser was not receiving power. I traced the low-voltage circuit and determined that the issue originated at the float switch. Although the float switch was not actively triggered, it was interrupting power to the condenser. I replaced the faulty float switch, restored power, and verified proper system operation.

At this time, the system is functioning normally. However, I recommend scheduling a preventive maintenance service, as the system is due for a full inspection and cleaning. Routine maintenance helps improve efficiency, extend equipment life, and reduce the likelihood of unexpected breakdowns.

Our maintenance membership program can help save money over time and includes additional benefits such as free service calls and 10% off parts and labor.

If you have any questions or concerns, please don’t hesitate to reach out. Thank you for your business, and have a great day.
Ace m.
Ace m. Checked in
Upon arrival, I found that the condenser was not receiving power. I traced the low-voltage circuit and determined that the issue originated at the float switch. Although the float switch was not actively triggered, it was interrupting power to the condenser. I replaced the faulty float switch, restored power, and verified proper system operation. At this time, the system is functioning normally. However, I recommend scheduling a preventive maintenance service, as the system is due for a full inspection and cleaning. Routine maintenance helps improve efficiency, extend equipment life, and reduce the likelihood of unexpected breakdowns. Our maintenance membership program can help save money over time and includes additional benefits such as free service calls and 10% off parts and labor. If you have any questions or concerns, please don’t hesitate to reach out. Thank you for your business, and have a great day.
St. Petersburg, FL 33703
Kyle K.
Kyle K. Checked in
Remove Current Supply Ducting Remove Mixing Boxes Duct Balancing & CFM Measurements Remove Collars & Couplers New Main Supply R6 Flex Install Mixing Boxes Install Couplers & Collars Install New R6 Supply Flex Ducting Strap All Ducting to Code Seal All Ducting to Code Seal Boots to Attic Ceiling 10 Year No Leak Guarantee *Complimentary air purifier for system
St. Petersburg, FL 33704
Tenant states that rooms were not cooling as well as the living room and the fan wouldn’t come on with the system. Tenant says they adjusted something but I could not get an answer about what they did exactly. On arrival found system satisfied at 71° in the middle of the day. Upon my inspection, found a very dirty air filter that required replacement. Tenant says they tried to keep house at 68° and it wouldn’t satisfy. I explained that they need to keep a clean air filter in place and it is hard to expect 68 out of a system in Florida. System has a good 20° temperature split. Found a weak capacitor. Recommended replacing the capacitor as well as a proper Maitenence on the system. Condenser coils are dirty and head pressure is higher than I’d like to see. 

Client would like to hold off on repairs and Maitenence.
Tenant states that rooms were not cooling as well as the living room and the fan wouldn’t come on with the system. Tenant says they adjusted something but I could not get an answer about what they did exactly. On arrival found system satisfied at 71° in the middle of the day. Upon my inspection, found a very dirty air filter that required replacement. Tenant says they tried to keep house at 68° and it wouldn’t satisfy. I explained that they need to keep a clean air filter in place and it is hard to expect 68 out of a system in Florida. System has a good 20° temperature split. Found a weak capacitor. Recommended replacing the capacitor as well as a proper Maitenence on the system. Condenser coils are dirty and head pressure is higher than I’d like to see. 

Client would like to hold off on repairs and Maitenence.
Michael A.
Michael A. Checked in
Tenant states that rooms were not cooling as well as the living room and the fan wouldn’t come on with the system. Tenant says they adjusted something but I could not get an answer about what they did exactly. On arrival found system satisfied at 71° in the middle of the day. Upon my inspection, found a very dirty air filter that required replacement. Tenant says they tried to keep house at 68° and it wouldn’t satisfy. I explained that they need to keep a clean air filter in place and it is hard to expect 68 out of a system in Florida. System has a good 20° temperature split. Found a weak capacitor. Recommended replacing the capacitor as well as a proper Maitenence on the system. Condenser coils are dirty and head pressure is higher than I’d like to see. Client would like to hold off on repairs and Maitenence.
St. Petersburg, FL 33703
St. Petersburg, FL - Performed maintenance on 1 system. Changed filters. Cleaned coil. Cleared pan and drain. Temp split good. Pressures good. Electrical checked good. Recommend to clean blower wheel. Will submit estimate for cleaning.
Justin G.
Justin G. Checked in
Performed maintenance on 1 system. Changed filters. Cleaned coil. Cleared pan and drain. Temp split good. Pressures good. Electrical checked good. Recommend to clean blower wheel. Will submit estimate for cleaning.
St. Petersburg, FL 33704
Upon arrival, I started by checking the temperature differential and measured a 20°F split, which is within the normal operating range. I then evaluated the refrigerant cycle and found no signs of leaks or restrictions at this time. Moving on to the electrical components, all readings were within manufacturer specifications, and no electrical issues were found.

I performed a drain line treatment, condenser coil cleaning, and a complete air handler inspection. The homeowner is already maintaining the system well with preventative maintenance measures in place. At this time, no repair recommendations are necessary, as the system is operating properly and all components appear to be functioning as designed.
Upon arrival, I started by checking the temperature differential and measured a 20°F split, which is within the normal operating range. I then evaluated the refrigerant cycle and found no signs of leaks or restrictions at this time. Moving on to the electrical components, all readings were within manufacturer specifications, and no electrical issues were found.

I performed a drain line treatment, condenser coil cleaning, and a complete air handler inspection. The homeowner is already maintaining the system well with preventative maintenance measures in place. At this time, no repair recommendations are necessary, as the system is operating properly and all components appear to be functioning as designed.
Ace m.
Ace m. Checked in
Upon arrival, I started by checking the temperature differential and measured a 20°F split, which is within the normal operating range. I then evaluated the refrigerant cycle and found no signs of leaks or restrictions at this time. Moving on to the electrical components, all readings were within manufacturer specifications, and no electrical issues were found. I performed a drain line treatment, condenser coil cleaning, and a complete air handler inspection. The homeowner is already maintaining the system well with preventative maintenance measures in place. At this time, no repair recommendations are necessary, as the system is operating properly and all components appear to be functioning as designed.
St. Petersburg, FL 33702
On arrival found unit not keeping up due to low refrigerant levels. Performed leak search on system and found leak in suction line. Made repairs. Pulled vacuum on system to check for leaks. Weighed in factory charge. Start and test. Unit cooling properly at this time.
On arrival found unit not keeping up due to low refrigerant levels. Performed leak search on system and found leak in suction line. Made repairs. Pulled vacuum on system to check for leaks. Weighed in factory charge. Start and test. Unit cooling properly at this time.
Justin G.
Justin G. Checked in
On arrival found unit not keeping up due to low refrigerant levels. Performed leak search on system and found leak in suction line. Made repairs. Pulled vacuum on system to check for leaks. Weighed in factory charge. Start and test. Unit cooling properly at this time.
St. Petersburg, FL 33704
Reason for call:
No cool mini split 

Equipment:
Single zone Mitsubishi mini split 

Summary:
Completed diagnosis to find a splice in com wire. This splice joint was holding a couple ounces of water. Unraveled tape to find corrosion on wire nut connections. Redid splice joints cut out corroded wires and resealed splice with new electrical tape all wire nuts points up to prevent this again. 

If problem persists we will have to replace com wire from indoor to outdoor units.
Reason for call:
No cool mini split 

Equipment:
Single zone Mitsubishi mini split 

Summary:
Completed diagnosis to find a splice in com wire. This splice joint was holding a couple ounces of water. Unraveled tape to find corrosion on wire nut connections. Redid splice joints cut out corroded wires and resealed splice with new electrical tape all wire nuts points up to prevent this again. 

If problem persists we will have to replace com wire from indoor to outdoor units.
Corbin C.
Corbin C. Checked in
Reason for call: No cool mini split Equipment: Single zone Mitsubishi mini split Summary: Completed diagnosis to find a splice in com wire. This splice joint was holding a couple ounces of water. Unraveled tape to find corrosion on wire nut connections. Redid splice joints cut out corroded wires and resealed splice with new electrical tape all wire nuts points up to prevent this again. If problem persists we will have to replace com wire from indoor to outdoor units.
St. Petersburg, FL 33704
Minor Duct seal
Minor Duct seal
Martin W.
Martin W. Checked in
Minor Duct seal
St. Petersburg, FL 33711
Diagnostic 
-outdoor unit going off on high pressure alarm due to fan motor not operating. Found capacitor failed causing unit not to run 

Scope of work 
-replaced failed outdoor capacitor 
-cleaned up service department 

Verified system operations after completing repairs. Unit is operating within manufacture specifications 

Further Notes 
-unit does not look to have had proper maintenance. Outdoor unit has debris inside condenser. Indoor drain has not been cleared.
Diagnostic 
-outdoor unit going off on high pressure alarm due to fan motor not operating. Found capacitor failed causing unit not to run 

Scope of work 
-replaced failed outdoor capacitor 
-cleaned up service department 

Verified system operations after completing repairs. Unit is operating within manufacture specifications 

Further Notes 
-unit does not look to have had proper maintenance. Outdoor unit has debris inside condenser. Indoor drain has not been cleared.
Nathan A.
Nathan A. Checked in
Diagnostic -outdoor unit going off on high pressure alarm due to fan motor not operating. Found capacitor failed causing unit not to run Scope of work -replaced failed outdoor capacitor -cleaned up service department Verified system operations after completing repairs. Unit is operating within manufacture specifications Further Notes -unit does not look to have had proper maintenance. Outdoor unit has debris inside condenser. Indoor drain has not been cleared.
St. Petersburg, FL 33702
Upon inspection, the blower motor is showing signs of intermittent failure and is nearing the end of its service life. I discussed the findings with the homeowner, and at this time they do not wish to invest in repairs. The homeowner would like to review replacement options with his wife before making a decision.

Please provide both a repair estimate and a full system replacement proposal. The homeowner has requested that we follow up on Monday to discuss the available options and next steps.
Upon inspection, the blower motor is showing signs of intermittent failure and is nearing the end of its service life. I discussed the findings with the homeowner, and at this time they do not wish to invest in repairs. The homeowner would like to review replacement options with his wife before making a decision.

Please provide both a repair estimate and a full system replacement proposal. The homeowner has requested that we follow up on Monday to discuss the available options and next steps.
Ace m.
Ace m. Checked in
Upon inspection, the blower motor is showing signs of intermittent failure and is nearing the end of its service life. I discussed the findings with the homeowner, and at this time they do not wish to invest in repairs. The homeowner would like to review replacement options with his wife before making a decision. Please provide both a repair estimate and a full system replacement proposal. The homeowner has requested that we follow up on Monday to discuss the available options and next steps.
St. Petersburg, FL 33714
Home owner states other company told them they need a condensate pump. Found indoor trap heavily backed up and line not properly cleared. Blew out line with nitrogen, cleared drain pan, added drain solve, added pan tablets to help with buildup. Unit is now clear and draining properly. Outdoor drain has backwards pitch. Put a piece of wood to weigh down drain for proper drainage. 

Checked indoor components for water damage. Plate beneath gas valve and components has rust due to water dripping on it. Unit is currently operating and no other issues at this time.
Home owner states other company told them they need a condensate pump. Found indoor trap heavily backed up and line not properly cleared. Blew out line with nitrogen, cleared drain pan, added drain solve, added pan tablets to help with buildup. Unit is now clear and draining properly. Outdoor drain has backwards pitch. Put a piece of wood to weigh down drain for proper drainage. 

Checked indoor components for water damage. Plate beneath gas valve and components has rust due to water dripping on it. Unit is currently operating and no other issues at this time.
Nathan A.
Nathan A. Checked in
Home owner states other company told them they need a condensate pump. Found indoor trap heavily backed up and line not properly cleared. Blew out line with nitrogen, cleared drain pan, added drain solve, added pan tablets to help with buildup. Unit is now clear and draining properly. Outdoor drain has backwards pitch. Put a piece of wood to weigh down drain for proper drainage. Checked indoor components for water damage. Plate beneath gas valve and components has rust due to water dripping on it. Unit is currently operating and no other issues at this time.
St. Petersburg, FL 33703
Upon arrival, I began by inspecting the condensate drain system and found that the float switch had been triggered. The secondary drain pan was completely full of water due to a clogged drain line. I cleared the blockage and performed a temporary startup to evaluate the system’s operation.

During testing, the system achieved a 17°F temperature split, which is within an acceptable operating range. All major components are currently functioning properly. However, the system was manufactured in 2003 and is well beyond its typical life expectancy. Due to the age and condition of the equipment, mechanical repairs are generally not recommended should a major component fail in the future.

I discussed the overall condition of the system with the homeowner and advised them to keep potential system replacement in mind as the equipment continues to age. To help monitor the system’s performance and catch issues before they become major problems, I offered a maintenance agreement that includes in
Upon arrival, I began by inspecting the condensate drain system and found that the float switch had been triggered. The secondary drain pan was completely full of water due to a clogged drain line. I cleared the blockage and performed a temporary startup to evaluate the system’s operation.

During testing, the system achieved a 17°F temperature split, which is within an acceptable operating range. All major components are currently functioning properly. However, the system was manufactured in 2003 and is well beyond its typical life expectancy. Due to the age and condition of the equipment, mechanical repairs are generally not recommended should a major component fail in the future.

I discussed the overall condition of the system with the homeowner and advised them to keep potential system replacement in mind as the equipment continues to age. To help monitor the system’s performance and catch issues before they become major problems, I offered a maintenance agreement that includes in
Ace m.
Ace m. Checked in
Upon arrival, I began by inspecting the condensate drain system and found that the float switch had been triggered. The secondary drain pan was completely full of water due to a clogged drain line. I cleared the blockage and performed a temporary startup to evaluate the system’s operation. During testing, the system achieved a 17°F temperature split, which is within an acceptable operating range. All major components are currently functioning properly. However, the system was manufactured in 2003 and is well beyond its typical life expectancy. Due to the age and condition of the equipment, mechanical repairs are generally not recommended should a major component fail in the future. I discussed the overall condition of the system with the homeowner and advised them to keep potential system replacement in mind as the equipment continues to age. To help monitor the system’s performance and catch issues before they become major problems, I offered a maintenance agreement that includes in
St. Petersburg, FL 33704
2017 Goodman Straight Cool

Diagnostic 
-drain line backing up causing system to intermittently cycle 
-outdoor capacitor very weak and rusted 

Scope of work 
-cut drain line and blow out with nitrogen 
-install clean out for tenant 
-clear drain pan & prime trap 
-added pan tablets to help with buildup 
-replaced outdoor 50/5 capacitor 

Further Notes 
-indoor air handler coils impacted with debris 
-outdoor coils corroded due to being close to water 
-outdoor contactor pitted and corroded 
-outdoor high voltage disconnect rusted & corroded 
-indoor disconnect marked bad

Verified system operations after completing work. System had a 16° temp split and cooling best of abilities 

Told home owner about system conditions and to look at replacing in future 


Discounted repairs from 695$ to 595$
2017 Goodman Straight Cool

Diagnostic 
-drain line backing up causing system to intermittently cycle 
-outdoor capacitor very weak and rusted 

Scope of work 
-cut drain line and blow out with nitrogen 
-install clean out for tenant 
-clear drain pan & prime trap 
-added pan tablets to help with buildup 
-replaced outdoor 50/5 capacitor 

Further Notes 
-indoor air handler coils impacted with debris 
-outdoor coils corroded due to being close to water 
-outdoor contactor pitted and corroded 
-outdoor high voltage disconnect rusted & corroded 
-indoor disconnect marked bad

Verified system operations after completing work. System had a 16° temp split and cooling best of abilities 

Told home owner about system conditions and to look at replacing in future 


Discounted repairs from 695$ to 595$
Nathan A.
Nathan A. Checked in
2017 Goodman Straight Cool Diagnostic -drain line backing up causing system to intermittently cycle -outdoor capacitor very weak and rusted Scope of work -cut drain line and blow out with nitrogen -install clean out for tenant -clear drain pan & prime trap -added pan tablets to help with buildup -replaced outdoor 50/5 capacitor Further Notes -indoor air handler coils impacted with debris -outdoor coils corroded due to being close to water -outdoor contactor pitted and corroded -outdoor high voltage disconnect rusted & corroded -indoor disconnect marked bad Verified system operations after completing work. System had a 16° temp split and cooling best of abilities Told home owner about system conditions and to look at replacing in future Discounted repairs from 695$ to 595$
St. Petersburg, FL 33715
Upon my inspection, downstairs unit is not keeping up with temperature. Found that the drain line was clogged. Performed a drain cleaning and treatment. Found that the drain line was very bad and had to take apart to clean. 30 day guarantee on drain cleaning. Maintenence is not due for another three months.
Upon my inspection, downstairs unit is not keeping up with temperature. Found that the drain line was clogged. Performed a drain cleaning and treatment. Found that the drain line was very bad and had to take apart to clean. 30 day guarantee on drain cleaning. Maintenence is not due for another three months.
Michael A.
Michael A. Checked in
Upon my inspection, downstairs unit is not keeping up with temperature. Found that the drain line was clogged. Performed a drain cleaning and treatment. Found that the drain line was very bad and had to take apart to clean. 30 day guarantee on drain cleaning. Maintenence is not due for another three months.
St. Petersburg, FL 33716
Replace warranty blower motor. Start and test. Tax and labor included.
Replace warranty blower motor. Start and test. Tax and labor included.
Ace m.
Ace m. Checked in
Replace warranty blower motor. Start and test. Tax and labor included.
St. Petersburg, FL 33704
Reason for call:
System not keeping up 

Equipment:
2019 trane 4 ton 
Vertical in garage 
Condenser on right side of home 

Summary:
On arrival I found system not going into second stage. Found no low voltage calling for second stage. Confirmed no calling at ah. Did continuity test between stage one and stage two of cooling. Confirmed wire was good. Related to a thermostat failed for calling on stage two.  Replace thermostat with ecobee thermostat. First stage two was restored. Proper pressures proper temperatures.
Reason for call:
System not keeping up 

Equipment:
2019 trane 4 ton 
Vertical in garage 
Condenser on right side of home 

Summary:
On arrival I found system not going into second stage. Found no low voltage calling for second stage. Confirmed no calling at ah. Did continuity test between stage one and stage two of cooling. Confirmed wire was good. Related to a thermostat failed for calling on stage two.  Replace thermostat with ecobee thermostat. First stage two was restored. Proper pressures proper temperatures.
Corbin C.
Corbin C. Checked in
Reason for call: System not keeping up Equipment: 2019 trane 4 ton Vertical in garage Condenser on right side of home Summary: On arrival I found system not going into second stage. Found no low voltage calling for second stage. Confirmed no calling at ah. Did continuity test between stage one and stage two of cooling. Confirmed wire was good. Related to a thermostat failed for calling on stage two. Replace thermostat with ecobee thermostat. First stage two was restored. Proper pressures proper temperatures.
St. Petersburg, FL 33702
Griffin K.
Griffin K. Checked in
Replace tripping ac breaker
St. Petersburg, FL 33709
Client state system stuff working yesterday. Upon my inspection, found bad capacitor and old contactor. Replaced both components and started system. Compressor and fan motor amp draws are good. Compressor startup amp draw is over camping. Let Client know that this may become a future issue. 
Pulling at this time with a 20° temperature split
Client state system stuff working yesterday. Upon my inspection, found bad capacitor and old contactor. Replaced both components and started system. Compressor and fan motor amp draws are good. Compressor startup amp draw is over camping. Let Client know that this may become a future issue. 
Pulling at this time with a 20° temperature split
Michael A.
Michael A. Checked in
Client state system stuff working yesterday. Upon my inspection, found bad capacitor and old contactor. Replaced both components and started system. Compressor and fan motor amp draws are good. Compressor startup amp draw is over camping. Let Client know that this may become a future issue. Pulling at this time with a 20° temperature split
St. Petersburg, FL 33702
Home owner states unit has had several issues since installed. Sub contractor installed unit.

Unit does not look to be professionally installed. Home owner has had several companies tell her same 

Air handler notes 
-no filter drier 
-no primary safety switch (potential water damage)

Outdoor notes 
-outdoor board failing 
-outdoor low pressure switch bypassed (switch has failed)

Went over issues with install and repairs needed. Went over options for new system 

Outdoor unit intermittently shutting off. Unit will continue to short cycle until repairs or replacement. Explained electric bill will be high.
Home owner states unit has had several issues since installed. Sub contractor installed unit.

Unit does not look to be professionally installed. Home owner has had several companies tell her same 

Air handler notes 
-no filter drier 
-no primary safety switch (potential water damage)

Outdoor notes 
-outdoor board failing 
-outdoor low pressure switch bypassed (switch has failed)

Went over issues with install and repairs needed. Went over options for new system 

Outdoor unit intermittently shutting off. Unit will continue to short cycle until repairs or replacement. Explained electric bill will be high.
Nathan A.
Nathan A. Checked in
Home owner states unit has had several issues since installed. Sub contractor installed unit. Unit does not look to be professionally installed. Home owner has had several companies tell her same Air handler notes -no filter drier -no primary safety switch (potential water damage) Outdoor notes -outdoor board failing -outdoor low pressure switch bypassed (switch has failed) Went over issues with install and repairs needed. Went over options for new system Outdoor unit intermittently shutting off. Unit will continue to short cycle until repairs or replacement. Explained electric bill will be high.
St. Petersburg, FL 33711
Upon my inspection, found capacitor, contactar, and wiring in the condenser burnt up and faulty. 
Replaced capacitor, contactar, and new connectors on wiring. 

System is cooling at this time with a 20° temp split. 
System is a 2010 and furnace is from 1992. Recommended that client prepare for new system due to age and condition. Sending quote over for replacement by tonight. 

No guarantee on repairs today due to system age and condition.
Upon my inspection, found capacitor, contactar, and wiring in the condenser burnt up and faulty. 
Replaced capacitor, contactar, and new connectors on wiring. 

System is cooling at this time with a 20° temp split. 
System is a 2010 and furnace is from 1992. Recommended that client prepare for new system due to age and condition. Sending quote over for replacement by tonight. 

No guarantee on repairs today due to system age and condition.
Michael A.
Michael A. Checked in
Upon my inspection, found capacitor, contactar, and wiring in the condenser burnt up and faulty. Replaced capacitor, contactar, and new connectors on wiring. System is cooling at this time with a 20° temp split. System is a 2010 and furnace is from 1992. Recommended that client prepare for new system due to age and condition. Sending quote over for replacement by tonight. No guarantee on repairs today due to system age and condition.
St. Petersburg, FL 33708
Check in with tower 175 to gain access. COI on file 

Maintenance needed to allow access for roof unit 

Home owner states she changed filter and unit stopped working. Home owner bumped wiring to secondary safety switch. Added wire nut and taped wires to side for home owner.

Performed tuneup on system 

Air handler notes
-coils heavily rusted 
-blower wheel & assembly accumulating bacterial growth 

Outdoor condenser notes 
-filter drier heavily rusted 
-coils starting to corrode 
-capacitor rusted and weak 
-contactor heavily pitted and rusted 

Rooftop units close to water
Check in with tower 175 to gain access. COI on file 

Maintenance needed to allow access for roof unit 

Home owner states she changed filter and unit stopped working. Home owner bumped wiring to secondary safety switch. Added wire nut and taped wires to side for home owner.

Performed tuneup on system 

Air handler notes
-coils heavily rusted 
-blower wheel & assembly accumulating bacterial growth 

Outdoor condenser notes 
-filter drier heavily rusted 
-coils starting to corrode 
-capacitor rusted and weak 
-contactor heavily pitted and rusted 

Rooftop units close to water
Nathan A.
Nathan A. Checked in
Check in with tower 175 to gain access. COI on file Maintenance needed to allow access for roof unit Home owner states she changed filter and unit stopped working. Home owner bumped wiring to secondary safety switch. Added wire nut and taped wires to side for home owner. Performed tuneup on system Air handler notes -coils heavily rusted -blower wheel & assembly accumulating bacterial growth Outdoor condenser notes -filter drier heavily rusted -coils starting to corrode -capacitor rusted and weak -contactor heavily pitted and rusted Rooftop units close to water
St. Petersburg, FL 33701
Full System Tuneup 

Unit is operating within manufacture specifications
Full System Tuneup 

Unit is operating within manufacture specifications
Nathan A.
Nathan A. Checked in
Full System Tuneup Unit is operating within manufacture specifications
St. Petersburg, FL 33702
Performed Maitenence on system. Cleaned/treated drain line and primary drain pan. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switch functionality. Checked amp draw on compressor. Checked amp draw on fan motor. Checked capacitor is within factory range. Inspected Contactar. Made sure all connections are tight. System is cooling with a 20° temperature split at this time.
Performed Maitenence on system. Cleaned/treated drain line and primary drain pan. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switch functionality. Checked amp draw on compressor. Checked amp draw on fan motor. Checked capacitor is within factory range. Inspected Contactar. Made sure all connections are tight. System is cooling with a 20° temperature split at this time.
Michael A.
Michael A. Checked in
Performed Maitenence on system. Cleaned/treated drain line and primary drain pan. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switch functionality. Checked amp draw on compressor. Checked amp draw on fan motor. Checked capacitor is within factory range. Inspected Contactar. Made sure all connections are tight. System is cooling with a 20° temperature split at this time.
St. Petersburg, FL 33703
Unit not cooling due to clogged drain line tripping safety. Cleared drain line and drain pan. Added pan tabs to help with buildup. Verified system operations and drainage. 

Home owner would like to move forward with maintenance plan
Unit not cooling due to clogged drain line tripping safety. Cleared drain line and drain pan. Added pan tabs to help with buildup. Verified system operations and drainage. 

Home owner would like to move forward with maintenance plan
Nathan A.
Nathan A. Checked in
Unit not cooling due to clogged drain line tripping safety. Cleared drain line and drain pan. Added pan tabs to help with buildup. Verified system operations and drainage. Home owner would like to move forward with maintenance plan
St. Petersburg, FL 33711
How do I know if my AC needs repair or full replacement?

Our technicians inspect the full system — age, refrigerant type, corrosion, and repair history — and give you an honest recommendation. If a repair makes sense, we'll fix it. If the unit is beyond its useful life, we'll walk you through replacement options with no pressure.

Are your technicians background-checked and licensed?

Yes. Every Air Bros technician is background-checked, factory-trained, and works under our state HVAC license (#CAC1820499) and electrical license (#EC13015085).

What parts of St. Petersburg do you serve?

We serve all of St. Petersburg, including Downtown, Historic Kenwood, Old Northeast, Snell Isle, Crescent Lake, Shore Acres, and Coquina Key, plus Seminole, Largo, Pinellas Park, and the surrounding beach communities.

Do you offer same-day AC repair in St. Petersburg?

Yes. We offer 24/7 emergency AC repair with same-day service throughout St. Petersburg and the surrounding Pinellas County area.

Is Air Bros a local St. Petersburg company, or a franchise?

Air Bros is 100% locally owned and operated, headquartered in the Shore Acres neighborhood of St. Petersburg. We're not a franchise — every technician is a direct employee, not a subcontractor.

Contact the Bros You Know Today!