Recent Jobs and Reviews in Palm Harbor , FL

Job Locations and Reviews

Maint plan
Arrived onsite and found 7 year old system leaking refrigerant from high pressure switch. I welded leak closed and vacuumed system. Charged with 9lbs of 410a and verified system is now operating properly
Maint plan
Arrived onsite and found 7 year old system leaking refrigerant from high pressure switch. I welded leak closed and vacuumed system. Charged with 9lbs of 410a and verified system is now operating properly
Ricky O.
Ricky O. Checked in
Maint plan Arrived onsite and found 7 year old system leaking refrigerant from high pressure switch. I welded leak closed and vacuumed system. Charged with 9lbs of 410a and verified system is now operating properly
Palm Harbor, FL 34683
Performed Maitenence on system. Cleaned/treated drain line and primary drain pan. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switch functionality. Checked amp draw on compressor. Checked amp draw on fan motor. Checked capacitor is within factory range. Inspected Contactar. Made sure all connections are tight. System is cooling with a 20° temperature split at this time.
System heating operations checked. 
Found growth on blower wheel and recommending cleaning/sanitation. Client would like to wait on cleaning. 

** system is over sized for size of home**
Performed Maitenence on system. Cleaned/treated drain line and primary drain pan. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switch functionality. Checked amp draw on compressor. Checked amp draw on fan motor. Checked capacitor is within factory range. Inspected Contactar. Made sure all connections are tight. System is cooling with a 20° temperature split at this time.
System heating operations checked. 
Found growth on blower wheel and recommending cleaning/sanitation. Client would like to wait on cleaning. 

** system is over sized for size of home**
Michael A.
Michael A. Checked in
Performed Maitenence on system. Cleaned/treated drain line and primary drain pan. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switch functionality. Checked amp draw on compressor. Checked amp draw on fan motor. Checked capacitor is within factory range. Inspected Contactar. Made sure all connections are tight. System is cooling with a 20° temperature split at this time. System heating operations checked. Found growth on blower wheel and recommending cleaning/sanitation. Client would like to wait on cleaning. ** system is over sized for size of home**
Palm Harbor, FL 34684
Performed Maitenence on system. Cleaned/treated drain line and primary drain pan. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switch functionality. Checked amp draw on compressor. Checked amp draw on fan motor. Checked capacitor is within factory range. Inspected Contactar. Made sure all connections are tight. System is cooling with a 22° temperature split at this time.

Found growth on the indoor blower wheel and inside air handler unit. Recommended a blower pull and clean as well as installing a UV system to prevent growth from returning.
Performed Maitenence on system. Cleaned/treated drain line and primary drain pan. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switch functionality. Checked amp draw on compressor. Checked amp draw on fan motor. Checked capacitor is within factory range. Inspected Contactar. Made sure all connections are tight. System is cooling with a 22° temperature split at this time.

Found growth on the indoor blower wheel and inside air handler unit. Recommended a blower pull and clean as well as installing a UV system to prevent growth from returning.
Michael A.
Michael A. Checked in
Performed Maitenence on system. Cleaned/treated drain line and primary drain pan. Cleaned condenser coils. Evaporator coils are clean. Verified safety float switch functionality. Checked amp draw on compressor. Checked amp draw on fan motor. Checked capacitor is within factory range. Inspected Contactar. Made sure all connections are tight. System is cooling with a 22° temperature split at this time. Found growth on the indoor blower wheel and inside air handler unit. Recommended a blower pull and clean as well as installing a UV system to prevent growth from returning.
Palm Harbor, FL 34683
Upon arrival, found AHU breaker tripped. Reset breaker, inspected wiring. Found insulation on back of AHU is peeling off. Unit has restricted air flow from dirty evaporator coils. Fan motor is at risk of failure. In heating mode this could be causing the amps to spike higher than normal and tripping the breaker. Recommending coil cleaning, fastening the insulation back to the unit. Also recommend replacing the breaker if the issue persists due to a weak breaker. 
Quotes sent for repairs and system replacement due to age of system. 
System is at risk of more failures due to age and there is no guarantee with these repairs. 
Verified heating and cooling work at this time.
Upon arrival, found AHU breaker tripped. Reset breaker, inspected wiring. Found insulation on back of AHU is peeling off. Unit has restricted air flow from dirty evaporator coils. Fan motor is at risk of failure. In heating mode this could be causing the amps to spike higher than normal and tripping the breaker. Recommending coil cleaning, fastening the insulation back to the unit. Also recommend replacing the breaker if the issue persists due to a weak breaker. 
Quotes sent for repairs and system replacement due to age of system. 
System is at risk of more failures due to age and there is no guarantee with these repairs. 
Verified heating and cooling work at this time.
Michael A.
Michael A. Checked in
Upon arrival, found AHU breaker tripped. Reset breaker, inspected wiring. Found insulation on back of AHU is peeling off. Unit has restricted air flow from dirty evaporator coils. Fan motor is at risk of failure. In heating mode this could be causing the amps to spike higher than normal and tripping the breaker. Recommending coil cleaning, fastening the insulation back to the unit. Also recommend replacing the breaker if the issue persists due to a weak breaker. Quotes sent for repairs and system replacement due to age of system. System is at risk of more failures due to age and there is no guarantee with these repairs. Verified heating and cooling work at this time.
Palm Harbor, FL 34683
-Pull and clean evap coil
-Pull and clean blower wheel
-Clean and sanitize inside of cabinet
-Duct sanitization
-All parts cleaned and sanitized 
-Install uv light 

Cleared drain line and re did wire nut connections 

Replace air handler motor capacitor (reading very weak)
-Pull and clean evap coil
-Pull and clean blower wheel
-Clean and sanitize inside of cabinet
-Duct sanitization
-All parts cleaned and sanitized 
-Install uv light 

Cleared drain line and re did wire nut connections 

Replace air handler motor capacitor (reading very weak)
Nathan A.
Nathan A. Checked in
-Pull and clean evap coil -Pull and clean blower wheel -Clean and sanitize inside of cabinet -Duct sanitization -All parts cleaned and sanitized -Install uv light Cleared drain line and re did wire nut connections Replace air handler motor capacitor (reading very weak)
Palm Harbor, FL 34683
Home owner states unit is not blowing air throughout house. Found failed air handler motor. Also found buildup in drain pan. Unit has not been serviced in 3 years. Recommend replacing motor in order to check pressures and temperature splits. 

Air purifiers installed backwards. Purifier with shield installed motor side when should be protecting 4” media filter. 
Clear Drain Line & Pan Complimentary  

Replaced air handler motor and verified operations 

Cleared drain line and drain pan
Home owner states unit is not blowing air throughout house. Found failed air handler motor. Also found buildup in drain pan. Unit has not been serviced in 3 years. Recommend replacing motor in order to check pressures and temperature splits. 

Air purifiers installed backwards. Purifier with shield installed motor side when should be protecting 4” media filter. 
Clear Drain Line & Pan Complimentary  

Replaced air handler motor and verified operations 

Cleared drain line and drain pan
Nathan A.
Nathan A. Checked in
Home owner states unit is not blowing air throughout house. Found failed air handler motor. Also found buildup in drain pan. Unit has not been serviced in 3 years. Recommend replacing motor in order to check pressures and temperature splits. Air purifiers installed backwards. Purifier with shield installed motor side when should be protecting 4” media filter. Clear Drain Line & Pan Complimentary Replaced air handler motor and verified operations Cleared drain line and drain pan
Palm Harbor, FL 34685
Upon my inspection, found indoor blower motor is not working. Verified high voltage and low voltage is supplied to the motor however the motor is not engaging. System is not cooling at this time and client requested to leave door panels off of unit. 
Quotes sent for blower replacement as well as system replacement with new warranties. 

Blower replacement requires extensive labor to remove due to poor serviceability access. Coil may need to be removed if motor cannot be detached from the blower housing within the unit.
Upon my inspection, found indoor blower motor is not working. Verified high voltage and low voltage is supplied to the motor however the motor is not engaging. System is not cooling at this time and client requested to leave door panels off of unit. 
Quotes sent for blower replacement as well as system replacement with new warranties. 

Blower replacement requires extensive labor to remove due to poor serviceability access. Coil may need to be removed if motor cannot be detached from the blower housing within the unit.
Michael A.
Michael A. Checked in
Upon my inspection, found indoor blower motor is not working. Verified high voltage and low voltage is supplied to the motor however the motor is not engaging. System is not cooling at this time and client requested to leave door panels off of unit. Quotes sent for blower replacement as well as system replacement with new warranties. Blower replacement requires extensive labor to remove due to poor serviceability access. Coil may need to be removed if motor cannot be detached from the blower housing within the unit.
Palm Harbor, FL 34683
On arrival found unit not running. Client states unit was not cooling day prior. Started unit. Unit is cooling. Found weak capacitor for condenser. Checked pressure and found unit to have restriction and not allow proper flow of refrigerant to flow through system. Tested compressor and it did not have proper ohms and is running hot. Recommend to replace compressor, capacitor, and clean piston to solve all existing issues. Will submit estimate for repair and replacement options. Unit is cooling at this time.
On arrival found unit not running. Client states unit was not cooling day prior. Started unit. Unit is cooling. Found weak capacitor for condenser. Checked pressure and found unit to have restriction and not allow proper flow of refrigerant to flow through system. Tested compressor and it did not have proper ohms and is running hot. Recommend to replace compressor, capacitor, and clean piston to solve all existing issues. Will submit estimate for repair and replacement options. Unit is cooling at this time.
Justin G.
Justin G. Checked in
On arrival found unit not running. Client states unit was not cooling day prior. Started unit. Unit is cooling. Found weak capacitor for condenser. Checked pressure and found unit to have restriction and not allow proper flow of refrigerant to flow through system. Tested compressor and it did not have proper ohms and is running hot. Recommend to replace compressor, capacitor, and clean piston to solve all existing issues. Will submit estimate for repair and replacement options. Unit is cooling at this time.
Palm Harbor, FL 34683
On arrival found unit not cooling due to clogged drain. Cleared pan and drain. Unit does not have primary float switch on system. Client declined adding one at this time. Coil clean. Blower clean. Added 1 lb of refrigerant to bring unit back to factory specs. Unit has 20* split. Unit cooling properly at this time.
On arrival found unit not cooling due to clogged drain. Cleared pan and drain. Unit does not have primary float switch on system. Client declined adding one at this time. Coil clean. Blower clean. Added 1 lb of refrigerant to bring unit back to factory specs. Unit has 20* split. Unit cooling properly at this time.
Justin G.
Justin G. Checked in
On arrival found unit not cooling due to clogged drain. Cleared pan and drain. Unit does not have primary float switch on system. Client declined adding one at this time. Coil clean. Blower clean. Added 1 lb of refrigerant to bring unit back to factory specs. Unit has 20* split. Unit cooling properly at this time.
Palm Harbor, FL 34683
Justin G.
Justin G. Checked in
Remove and replace warranty evaporator coil and filter dryer. Pull vacuum on system to verify no leaks and remove contaminants. Add refrigerant back to factory specs. Tax and labor included. Perform complimentary tune up.
Palm Harbor, FL 34683
On arrival found unit not cooling properly due to low on refrigerant. Performed leak search and found unit leaking in evaporator coil. Client declined adding refrigerant at this time. Will return to replace coil. Found blower wheel extremely impacted. Client declined cleaning. Unit cooling to the best of its ability at this time.
On arrival found unit not cooling properly due to low on refrigerant. Performed leak search and found unit leaking in evaporator coil. Client declined adding refrigerant at this time. Will return to replace coil. Found blower wheel extremely impacted. Client declined cleaning. Unit cooling to the best of its ability at this time.
Justin G.
Justin G. Checked in
On arrival found unit not cooling properly due to low on refrigerant. Performed leak search and found unit leaking in evaporator coil. Client declined adding refrigerant at this time. Will return to replace coil. Found blower wheel extremely impacted. Client declined cleaning. Unit cooling to the best of its ability at this time.
Palm Harbor, FL 34683
Michael A.
Michael A. Checked in
cleaned condenser coils
Palm Harbor, FL 34685
Palm Harbor, FL - Upon my inspection, I found a clogged drain line and dirty condenser coils. Client would like to proceed with cleaning condenser coils but would like to fix drain issue themselves.
Michael A.
Michael A. Checked in
Upon my inspection, I found a clogged drain line and dirty condenser coils. Client would like to proceed with cleaning condenser coils but would like to fix drain issue themselves.
Palm Harbor, FL 34685
Palm Harbor, FL - member tuneup
Checked refrigerant pressures and air temperature split. Tested capacitor -capacitor is weak- replaced during today’s maintenance. Cleaned condenser electrical cabinet and washed condenser coil. Flushed vacuumed and treated condensate drain line. Air handler interior is clean. No other issues at this time.
Sha’nya B.
Sha’nya B. Checked in
member tuneup Checked refrigerant pressures and air temperature split. Tested capacitor -capacitor is weak- replaced during today’s maintenance. Cleaned condenser electrical cabinet and washed condenser coil. Flushed vacuumed and treated condensate drain line. Air handler interior is clean. No other issues at this time.
Palm Harbor, FL 34685
No cool
Found float switch tripped, clogged drain line
Flushed vacuumed and cleaned drain line
Treated drain pan and left pan tabs
Tested system function after repair
No cool
Found float switch tripped, clogged drain line
Flushed vacuumed and cleaned drain line
Treated drain pan and left pan tabs
Tested system function after repair
Sha’nya B.
Sha’nya B. Checked in
No cool Found float switch tripped, clogged drain line Flushed vacuumed and cleaned drain line Treated drain pan and left pan tabs Tested system function after repair
Palm Harbor, FL 34683
Ricky O.
Ricky O. Checked in
Replace warranty cap
Palm Harbor, FL 34683

Contact the Bros You Know Today!

Schedule Service Online
servicedetailscustomerreturningschedule
*
Details Regarding Your Request...
Optional: Drag and drop photos and/or videos:
Max. file size: 4 MB.
Your Contact and Service Location...
*
*
*
To Serve You Best...
Have we served you in the past?
Yes
No
*
What Is Convenient For You?
*
What time of day is best for you?
First Available
Morning
Afternoon
*

Call For Same Day Service/Emergencies at 727-217-6148 .

By pressing Submit I agree to receive phone, email, or text messages from Air Bros Air Conditioning & Heating to the provided mobile number and also agree to the Air Bros Air Conditioning & Heating terms and privacy policy. Message & data rates may apply. Consent is not a condition of purchase. We will never share your personal information with third parties for marketing purposes.
Back Next